Plan Review Notes For Permit 11100642 |
Permit Number |
11100642 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-11-08 16:55:42 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PERMIT APPLICATION INDECATES THAT THIS WORK | | CONSTITUTES A CHANGE OF OCCUPANCY OR USE. PROVIDE DATA | | TO SHOW VENTILATION REQUIREMENTS FOR THE NEW PROPOSED | | OCCUPANCY IN ACCORDANCE WITH FBC-EB SECTION 908 AND | | FBC-M SECTION 403. | | | | 2. PROVIDE MAKE AND EFFICIENCY RATING OF PROPOSED HVAC | | APPLIANCES PER FBC-M 301.2. | | | | 3. SHOW SIZE AND LOCATION OF OUTSIDE AIR INTAKE FOR | | VENTILATION TO SHOW COMPLIANCE WITH FBC-M 401.4. | | | | 4. PLAN CALLS FOR LOUVERED DOOR ON AC CLOSET. THIS | | CLOSET CONSTITUTES A PLENUM. WHAT MATERIAL IS THE | | LOUVER DOOR? COMBUSTIBLE MATERIALS SHALL NOT BE EXPOSED | | IN A PLENUM PER FBC-M 602.2.1. | | | | 5. HVAC NOTES CALL FOR AN APPROVED ROOF STAND. | | PRE-ENGINEERED A/C STANDS REQUIRE PRODUCT APPROVAL PER | | FAC RULE 9N-1. SUBMIT PRODUCT APPROVAL DOCUMENTATION | | FOR STAND TO BE USED. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|