2011-11-08 16:55:42REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PERMIT APPLICATION INDECATES THAT THIS WORK
 CONSTITUTES A CHANGE OF OCCUPANCY OR USE. PROVIDE DATA
 TO SHOW VENTILATION REQUIREMENTS FOR THE NEW PROPOSED
 OCCUPANCY IN ACCORDANCE WITH FBC-EB SECTION 908 AND
 FBC-M SECTION 403.
  
 2. PROVIDE MAKE AND EFFICIENCY RATING OF PROPOSED HVAC
 APPLIANCES PER FBC-M 301.2.
  
 3. SHOW SIZE AND LOCATION OF OUTSIDE AIR INTAKE FOR
 VENTILATION TO SHOW COMPLIANCE WITH FBC-M 401.4.
  
 4. PLAN CALLS FOR LOUVERED DOOR ON AC CLOSET. THIS
 CLOSET CONSTITUTES A PLENUM. WHAT MATERIAL IS THE
 LOUVER DOOR? COMBUSTIBLE MATERIALS SHALL NOT BE EXPOSED
 IN A PLENUM PER FBC-M 602.2.1.
  
 5. HVAC NOTES CALL FOR AN APPROVED ROOF STAND.
 PRE-ENGINEERED A/C STANDS REQUIRE PRODUCT APPROVAL PER
 FAC RULE 9N-1. SUBMIT PRODUCT APPROVAL DOCUMENTATION
 FOR STAND TO BE USED.
  