Plan Review Notes
Plan Review Notes For Permit 11100642
Permit Number 11100642
Review Stop B
Sequence Number 1
Notes
Date Text
2011-11-07 15:02:29BUILDING PLAN REVIEW
 PERMIT: 11100642
 ADD: 946 BELVEDERE RD
 CONT: CONSTRUCTION REMODELING 1
 TEL: (561)667-9924
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLEASE REVIEW THE PROPERTY APPRAISERS SITE IT
 APPEARS THE PARKING LOTS TO THE EASR AND WEST ARE
 DIFFERENT PROPERTY CONTROL NUMBERS, IT APPEARS THIS IS
 A ZERO LOT LINE BUILDING TO THE EAST AND WEST SIDES OF
 THE BUILDING WHICH WOULD NOT ALLOW WINDOW AND DOOR
 OPENINGS ON BOTH THE EAST & WEST SIDES OF THE BUILDING.
 EITHER A SURVEY INDICATING THE CLOSENESSS OF THE
 PROPERTY LINES AND SHOW ING COMPLIANCE WITH FBC-B TABLE
 602 AND TABLE 704.8 MAXIMUM AREA OF EXTERIOR WALL
 OPENINGS, OR PROVIDE A UNITY OF TITLE COMBINING THE
 THREE LOTS INTO ONE LOT. THE UNITY OF TITLE FORMS CAN
 BE PICKED UP AT THE CITY OF WPB ENGINEERING DEPARTMENT
 TO BE FILLED OUT RECORDED AT THE CLERK OF THE COURT AND
 COPIES SUBMITTED TO CONSTRUCTIONS SERVICES DEPARTMENT
 AND ENGINEERING OR GO ON LINE AND DOWN LOAD THE FORM
 FROM:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 "APPLICATION FOR UNITY OF TITLE"
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
 1B) PLEASE NOTE THE OCCUPANT LOAD WILL BE 51 OCCUPANTS,
 (49 MERCANTILE + 2 BUSINESS) WHICH WILL REQUIRE 2
 EGRESS DOORS 1/2 THE DIAGONAL APART. FBC-B TABLE 1015.1
 & SECTION 1015.2.1.
  
 1C) PLANS SHOW A DOUBLE DASHED LINE ON THE FLOOR PLAN,
 PLEASE PROVIDE ADDITIONAL INFORMATION. 106.1.2.
  
 2) DEPENDING ON THE OUTCOME OF COMMENT NUMBER ONE AND
 OPENINGS WILL BE ALLOWED ON THE SIDES OF THE BUILDING
 THE FOLLOWING CRITERIA WILL BE REQUIRED.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
  
 3) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
  
 3A) EXTERIOR DOORS
  
 3B) EXTERIOR WINDOWS
  
 3C) WINDOW MULLION REPORT IF NOT INCLUDED IN THE WINDOW
 REPORT
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) BOTH THE WINDOW AND DOOR BUCK DETAILS INDICATE THE
 USE OF 45 DEGREE CUTS NOT ALLOWING BOTH LEGS OF THE
 FRAME TO SET ON THE SUB-FRAMING. FBC-B 1714.5.4.2
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED.
  
 1714.5.4.3 WOOD OR OTHER APPROVED FRAMING MATERIALS.
 WHERE THE FRAMING MATERIAL IS WOOD OR OTHER APPROVED
 FRAMING MATERIAL, WINDOW AND GLASS DOOR ASSEMBLIES
 SHALL BE ANCHORED THROUGH THE MAIN FRAME OR BY JAMB
 CLIP OR SUBFRAME SYSTEM OR THROUGH THE FLANGE IN
 ACCORDANCE WITH THE MANUFACTURER'S PUBLISHED
 INSTALLATION INSTRUCTIONS.
  
 6) THE SCOPE OF WORK AND VALUE ATTACHED TO THE SCOPE OF
 WORK APPEARS LOW IN VALUE. THIS WILL EFFECT THE AMOUNT
 DUE TO DISPROPORTIONALITY.
 THE DUTY TO PROVIDE ACCESSIBILITY PLEASE SHOW HOW
 COMPLIANCE WITH SECTION 11-4.1.6.(2) ALTERATIONS MADE
 TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20 PERCENT OF THE COST
 OF THE ALTERATION TO THE PRIMARY FUNCTION AREA.
  
 DUTY TO PROVIDE ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 (1) WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE
 PATH OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS.
  
 (2)(A) IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER:
  
 (I) AN ACCESSIBLE ENTRANCE;
  
 (II) AN ACCESSIBLE ROUTE TO THE ALTERED AREA:
  
 (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR
 A SINGLE UNISEX RESTROOM:
  
 (IV) ACCESSIBLE TELEPHONES;
  
 (V) ACCESSIBLE DRINKING FOUNTAINS; AND
  
 (VI) WHEN POSSIBLE, ADDITIONAL ACCESSIBLE ELEMENTS SUCH
 AS PARKING, STORAGE, AND ALARMS.
  
 PLEASE PROVIDE WHERE OR HOW $1,500.00 DOLLARS ABOVE THE
 CONTRACT VALUE WILL BE USED TO COMPLY WITH
 ACCESSIBLITY.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  