2011-10-28 14:03:33330 CLEMATIS STREET - SUITE #107
 PERMIT #11100639
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ADD SUITE NUMBER TO DRAWING ADDRESS TITLEBLOCK.
  
 SUBMIT PRODUCT DATA ON SPRINKLERS AND FLEXIBLE DROPS.
  
 PROVIDE DRY PENDENT SPRINKLERS IN COOLER.
  
 THE 9'-0" AFF SOFFIT ADJACENT TO THE RESTROOMS DO NOT
 APPEAR TO HAVE SPRINKLER PROTECTION.
  
 SUBMIT HYDRAULIC CALCULATIONS SUPPORTING THE ADDITIONAL
 FRICTION LOSS ASSOCIATED WITH THE FLEXIBLE DROPS.
  
 INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROPS TO BE
 USED.
  
 FLEXHEAD DETAIL: INDICATE THE MINIMUM BENDING RADIUS
 AND MAXIMUM NUMBER OF BENDS PER THE LISTING
 REQUIREMENTS.
  
 NOTE: PER LOCAL AHJ POLICY, ONLY BRAIDED FLEXIBLE DROPS
 ARE ACCEPTED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  