2011-11-07 13:30:58BUILDING PLAN REVIEW
 PERMIT: 11100633
 ADD: 4325 N HAVERHILL RD
 CONT: WESLEY CONSTRUCTION
 TEL: (561)318-1061
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 A) PLANS SUMITTED INDICATE TWO PROJECTS, THE MAINTENCE
 BUILDING AND CONTROL BUILDING ONLY ONE SET OF PLANS
 WERE SUBMITTED FOR EACH PROJECT. WPB ADMINISTRATIVE
 CODE 106.3.1 REQUIRES TWO SETS FOR EACH PROJECT.
  
 B) THE CONTRACTOR OF RECORD SHOULD APPLY FOR TWO
 INDIVIDUAL PERMIT ONE FOR EACH LOCATION, THE MAITENCE
 BUILDING AND ONE PERMIT FOR THE CONTROL BUILDING. THIS
 WILL ALLOW THE INSPECTION CODES TO BE SEPERATED FOR
 EACH BUILDING AND THE PLAN REVIEW AS WELL AS INSPECTION
 HISTORY TO BE TRACKED SEPERATELY.
  
 THE FIRST PORTION OF THIS REVIEW WILL BE FOR THE :
  
 CONTROL BUILDING
  
 2)) 106.3.5(1)(3). MINIMUM TYPE OF CONSTRUCTION SHALL
 BE DETERMINED (SEE TABLE 503).
  
 3) 106.3.5(8)STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WIND REQUIREMENTS, MISSING WIND DESIGN CRITERIA:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
  
 4) PLANS INDICATE THE USE OF A EXTERIOR METAL STUD WALL
 SYSTEM BUT THERE IS NO DESIGN INFORMATION HOW THE TOP
 AND BOTTOM TRACKS WILL BE ANCHORED TO RESIST WIND.
 SHEET A3 DETAIL 1 INDICATES THE ROOF STRUCTURE TO BE
 CONCRETE JOIST WITH STEEL TENDON REINFORCING BUT NO
 INFORMATION AS TO HOW TO ANCHOR TO THE EXISTING
 CONCRETE JOIST SYSTEM?
 FBC-B 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO
 RESIST THE OVERTURNING EFFECTS CAUSED BY LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND .
  
 5) THE PRODUCT APPROVAL SUBMITTED IS A MIAMI-DADE NOA
 09-1217.05 FOR SINGLE HUNG WINDOWS PLEASE REVIEW SHEET
 2 OF 6 DETAIL A3 FOR ATTACHMENT TO METAL STRUCTURAL
 METAL.
 THE DETAIL INDICATES A MINIMUM STEEL OR ALUMINUM
 THICKNESS OF 1/8TH (0.125) INCH. THE METAL STUD
 INDICATED ON THE PLANS IS 600S162-54 0.0566 INCHES,
 PLEASE REVIEW THE PRODUCT APPROVAL REQUIREMENTS.
  
 6) PLEASE REVIEW SHEETA3 DETAIL A IT APPEARS THE WINDOW
 TO BE A STOREFRONT DESIGN NOT THE SING HUNG WINDOW THE
 PRODUCT APPROVAL IS FOR. DISCREPANCY.
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 MAINTENENCE BUILDING
 THE SAME COMMENTS 1-6. WILL REQUIRE A SEPERATE PERMIT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]