2011-11-07 13:30:58 | BUILDING PLAN REVIEW |
| PERMIT: 11100633 |
| ADD: 4325 N HAVERHILL RD |
| CONT: WESLEY CONSTRUCTION |
| TEL: (561)318-1061 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| A) PLANS SUMITTED INDICATE TWO PROJECTS, THE MAINTENCE |
| BUILDING AND CONTROL BUILDING ONLY ONE SET OF PLANS |
| WERE SUBMITTED FOR EACH PROJECT. WPB ADMINISTRATIVE |
| CODE 106.3.1 REQUIRES TWO SETS FOR EACH PROJECT. |
| |
| B) THE CONTRACTOR OF RECORD SHOULD APPLY FOR TWO |
| INDIVIDUAL PERMIT ONE FOR EACH LOCATION, THE MAITENCE |
| BUILDING AND ONE PERMIT FOR THE CONTROL BUILDING. THIS |
| WILL ALLOW THE INSPECTION CODES TO BE SEPERATED FOR |
| EACH BUILDING AND THE PLAN REVIEW AS WELL AS INSPECTION |
| HISTORY TO BE TRACKED SEPERATELY. |
| |
| THE FIRST PORTION OF THIS REVIEW WILL BE FOR THE : |
| |
| CONTROL BUILDING |
| |
| 2)) 106.3.5(1)(3). MINIMUM TYPE OF CONSTRUCTION SHALL |
| BE DETERMINED (SEE TABLE 503). |
| |
| 3) 106.3.5(8)STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| WIND REQUIREMENTS, MISSING WIND DESIGN CRITERIA: |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| |
| 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| |
| 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| |
| 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| |
| 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL. |
| |
| 4) PLANS INDICATE THE USE OF A EXTERIOR METAL STUD WALL |
| SYSTEM BUT THERE IS NO DESIGN INFORMATION HOW THE TOP |
| AND BOTTOM TRACKS WILL BE ANCHORED TO RESIST WIND. |
| SHEET A3 DETAIL 1 INDICATES THE ROOF STRUCTURE TO BE |
| CONCRETE JOIST WITH STEEL TENDON REINFORCING BUT NO |
| INFORMATION AS TO HOW TO ANCHOR TO THE EXISTING |
| CONCRETE JOIST SYSTEM? |
| FBC-B 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO |
| RESIST THE OVERTURNING EFFECTS CAUSED BY LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND . |
| |
| 5) THE PRODUCT APPROVAL SUBMITTED IS A MIAMI-DADE NOA |
| 09-1217.05 FOR SINGLE HUNG WINDOWS PLEASE REVIEW SHEET |
| 2 OF 6 DETAIL A3 FOR ATTACHMENT TO METAL STRUCTURAL |
| METAL. |
| THE DETAIL INDICATES A MINIMUM STEEL OR ALUMINUM |
| THICKNESS OF 1/8TH (0.125) INCH. THE METAL STUD |
| INDICATED ON THE PLANS IS 600S162-54 0.0566 INCHES, |
| PLEASE REVIEW THE PRODUCT APPROVAL REQUIREMENTS. |
| |
| 6) PLEASE REVIEW SHEETA3 DETAIL A IT APPEARS THE WINDOW |
| TO BE A STOREFRONT DESIGN NOT THE SING HUNG WINDOW THE |
| PRODUCT APPROVAL IS FOR. DISCREPANCY. |
| 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| MAINTENENCE BUILDING |
| THE SAME COMMENTS 1-6. WILL REQUIRE A SEPERATE PERMIT. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |