Plan Review Notes
Plan Review Notes For Permit 11100547
Permit Number 11100547
Review Stop B
Sequence Number 2
Notes
Date Text
2011-11-01 09:56:24RE-ROOF SUBMITTAL FOR ALTERNATIVE MATERIALS AND METHODS
 BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
  
  
 ALTERNATIVE MATERIALS AND METHODS INSTALLATION IS
 APPROVED BY ROBERT BROWN (ASSISTANT BUILDING OFFICIAL).
 THE FOLLOWING INFORMATION IS REQUIRED BY HIM TO APPROVE
 PROPOSED INSTALLATION: IF YOU HAVE ANY QUESTIONS,
 PLEASE CALL ROBERT BROWN AT (561)805-6652.
  
 1- TABLE 3 OF TILE NOA 07-0914.13 HAS 3:12 MIN. SLOPE.
 EXISTING ROOF IS 2:12 SLOPE. ENGINEER IS USING THE
 RESTORING MOMENT FOR A 3:12 PITCH. ENGINEER TO PROVIDE
 CALCULATIONS SHOWING HOW OBTAINING THE RESTORING MOMENT
 FOR A 2:12 PITCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC.
  
  
 2- NEED TO SHOW COMPATIBILITY OF AH160 FOAM WITH THE
 SELECTED FLAT ROOF SYSTEM CAP SHEET. NEED
 MANUFACTURER'S INSTALLATION INSTRUCTIONS OR OTHER
 JUSTIFICATION FOR COMPATIBILITY.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712