Plan Review Notes
Plan Review Notes For Permit 11100547
Permit Number 11100547
Review Stop B
Sequence Number 1
Notes
Date Text
2011-10-26 13:25:26RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- CLAY TILE CAN'T BE INSTALLED IN 2:12 ROOF PITCH.
 SEC. R905.3.2 AND FRSA/TRI 07320.
 NEED PRODUCT APPROVAL FOR ROOF TYPE THAT CAN BE
 INSTALLED ON EXISTING ROOF SLOPE.
  
 2- CLARIFY WHY RE-ROOFING THE REAR PATIO ROOF ONLY.
 NEED TO VERIFY COMPLIANCE WITH SEC. 611 OF 2007
 FBC-EXISTING BUILDING. ENTIRE HOUSE MAY NEED TO BE
 RE-ROOFED.
 ***NOTE: IF COMPLETE HOUSE RE-ROOF IS REQUIRED, THEN
 THE ROOF TO WALL CONNECTIONS SECTION NEED TO BE
 ADDRESSED ALSO. HOUSE VALUE IS MORE THAN #300,000. SEC.
 611.8 EXISTING BUILDING CODE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712