2011-11-07 08:51:3711100546
 429 BELEVEDERE RD
 ELECTRICAL SERVICE WORK
  
 VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE AT THE LINE TERMINALS OF THE
 EQUIPMENT. NEC 110.9
 VERIFY THE EXISTING SERVICE RISER HAS ADEQUATE SIZE AND
 CLEARANCE. NEC 230.24
 INDICATE THE WIRE SIZE REQUIRED FOR THE SERVICE RISER.
 NEC 310.16
 VERIFY THAT ALL MAIN SERVICE DISCONNECTS ARE GROUPED IN
 ONE LOCATION. SHOW SERVICE LOCATION ON THE PLAN. NEC
 230.72
 SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5
  