2011-10-26 14:25:01 | **PROVISO** | | | | TRANSFER GRILL BETWEEN FAMILY AND DINING TOO SMALL TO | | MEET THE BALANCED RETURN AIR EXCEPTIONS UNDER FBC-M | | 601.4. INCREASE GRILL SIZE TO MEET THE EXCEPTION OR A | | FIELD TEST WILL BE REQUIRED TO VERIFY BALANCED RETURN. |
|