2012-01-13 13:30:26BUILDING PLAN REVIEW
 PERMIT: 11100370
 ADD: 215 CLEMATIS ST
 CONT: L B DEVELOPMENT
 TEL: (954)709-1926
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 01/13/2012
 3RD REVIEW
 ACTION: APPROVED
  
 1) PROVISO:THE MEZZANINE AND KITCHEN BELOW MUST
 MAINTAIN A FINISHED CEILING HEIGHT OF 7'-0" FBC-B
 1208.2 EXCEPTION # 3. SHEET A-3 STILL INDICATES A 6'-8"
 DIMENSION.
  
 2-4) COMPLIED.
  
  
  
 5) BUILDING PROVISO:
 MISSING PRODUCT APPROVALS FBC-B 1609 COMPONENTS &
 CLADDING, RULE 9N-3.
 5A-B) COMPLIED.
 5C) EXTERIER WALK IN COOLERS &/FREEZERS
  
 6-12) COMPLIED.
  
 13) PROVISO: A SEPERATE PREMIT IS REQUIRED. SHEET A-3 &
 A-4 INDICATE THE USE OF DRYWALL DROPED CEILING PANELS
 WITH LATTICE, A NOTE ON A-3 INDICATES METHOD OF
 ATTACHMENT, SUSPENSION BY OTHERS, THIS SYSTEM TO BE
 REVIEWED BY THE DESIGN PROFESSIONAL, IT CAN BE
 PERMITTED UNDER THIS PERMIT OR COME IN AS A STAND ALONE
 PERMIT. THE DROPPED CEILING WILL NEED TO SHOW
 COMPLIANCE WITH
 803.3 & 803.4.1 AND MEET THE FINISH REQUIREMENTS OF
 TABLE 803.5.
  
 14-15) COMPLIED.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER