Plan Review Notes For Permit 11100370 |
Permit Number |
11100370 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-01-11 12:48:19 | 215 CLEMATIS STREET | | PERMIT #11100370 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | REPEAT COMMENT: SHEET A-2 (DOOR #2 AND #6): DURING ITS | | SWING, ANY DOOR IN A MEANS OF EGRESS SHALL PROJECT NOT | | MORE THAN 7-INCHES INTO THE REQUIRED WIDTH OF THE | | EGRESS PATH WHEN FULLY OPEN. WHEN FULLY OPEN THESE DOOR | | PROJECT MORE THAN 7-INCHES INTO THE CORRIDOR. | | | | REPEAT COMMENT: INTERIOR WALL FINISHES AND CEILING | | FINISHES SHALL MEET AT LEAST A CLASS C RATING FOR FLAME | | SPREAD AND SMOKE DEVELOPEMENT. | | | | PROVIDE DETAIL OR PRODUCT DATA FOR THE SUSPENDED WOOD | | TRELLIS. INDICATE IF ANY DECORATIONS, PLANTS, FABRICS, | | ETC. WILL BE USED TO DECORATE THE TRELLIS. | | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY | | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING | | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM | | WWW.KNOXBOX.COM. | | | | DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE | | FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE | | BEEN SATISFIED. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW |
|