2012-01-06 09:51:34 | BUILDING PLAN REVIEW |
| PERMIT: 11100370 |
| ADD: 215 CLEMATIS ST |
| CONT: L B DEVELOPMENT |
| TEL: (954)709-1926 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 01/06/2012 |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1) THE MEZZANINE AND KITCHEN BELOW MUST MAINTAIN A |
| FINISHED CEILING HEIGHT OF 7'-0" FBC-B 1208.2 EXCEPTION |
| # 3. SHEET A-3 STILL INDICATES A 6'-8" DIMENSION. |
| |
| 2) NO FIRE SPRINKLER PLANS WERE SUBMITTED. THE LAST |
| KNOWN USE OF THIS SPACE WAS A DRESS SHOP MAKING THIS A |
| CHANGE OF OCCUPANCY. THE 2007/09 FBC EXISTING BUILDING |
| CODE CHAPTER 9 CHANGE OF OCCUPANCY SECTION EXST BLDG |
| COE 904.1 . FIRE PROTECTION REQUIREMENTS OF SECTION 912 |
| SHALL APPLY WHERE A BUILDING OR PORTIONS THEREOF |
| UNDERGO A CHANGE OF OCCUPANCY CLASSIFICATION. |
| |
| EXST BLDG CODE 912.2 FIRE PROTECTION SYSTEMS. FIRE |
| PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH |
| SECTIONS 912.2.1 AND 912.2.2. |
| |
| 2A) EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. WHERE |
| A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , SUCH |
| SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| CHANGE OF OCCUPANCY OCCURS. |
| |
| 2007/09 FBC-B 903.2 WHERE REQUIRED. APPROVED AUTOMATIC |
| SPRINKLER SYSTEMS IN NEW BUILDINGS AND STRUCTURES SHALL |
| BE PROVIDED IN THE LOCATIONS DESCRIBED IN THIS SECTION. |
| FBC-B 903.2.1.2 GROUP A-2. AN AUTOMATIC SPRINKLER |
| SYSTEM SHALL BE PROVIDED FOR GROUP A-2 OCCUPANCIES |
| WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS: |
| 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2). |
| 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE. |
| 3. THE FIRE AREA IS LOCATED ON A FLOOR OTHER THAN THE |
| LEVEL OF EXIT DISCHARGE. |
| 4. NIGHTCLUBS OR SIMILAR USAGE WHEN OCCUPANT LOAD IS |
| 100 OR MORE. |
| 903.3 INSTALLATION REQUIREMENTS. AUTOMATIC SPRINKLER |
| SYSTEMS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE |
| WITH SECTIONS 903.3.1 THROUGH 903.3.7. |
| 903.4 SPRINKLER SYSTEM MONITORING AND ALARMS. ALL |
| VALVES CONTROLLING THE WATER SUPPLY FOR AUTOMATIC |
| SPRINKLER SYSTEMS, PUMPS, TANKS, WATER LEVELS AND |
| TEMPERATURES, CRITICAL AIR PRESSURES AND WATER-FLOW |
| SWITCHES ON ALL SPRINKLER SYSTEMS SHALL BE ELECTRICALLY |
| SUPERVISED IN ACCORDANCE WITH NFPA 72. |
| 903.4.1 SIGNALS. ALARM, SUPERVISORY AND TROUBLE SIGNALS |
| SHALL BE DISTINCTLY DIFFERENT AND AUTOMATICALLY |
| TRANSMITTED TO AN APPROVED CENTRAL STATION, REMOTE |
| SUPERVISING STATION OR PROPRIETARY SUPERVISING STATION |
| AS DEFINED IN NFPA 72 OR, WHEN APPROVED BY THE FIRE |
| CODE OFFICIAL, SHALL SOUND AN AUDIBLE SIGNAL AT A |
| CONSTANTLY ATTENDED LOCATION. |
| |
| |
| 2B) COMPLIED. FIRE ALAARM PLAANS WERE SUBMITTED. |
| |
| 3) COMPLIED. |
| |
| 4) COMPLIED. |
| |
| 5) MISSING PRODUCT APPROVALS FBC-B 1609 COMPONENTS & |
| CLADDING, RULE 9N-3. |
| 5A-B) COMPLIED. |
| 5C) EXTERIER WALK IN COOLERS &/FREEZERS |
| |
| 6-12) COMPLIED. |
| |
| 13) PROVISO: A SEPERATE PREMIT IS REQUIRED. SHEET A-3 & |
| A-4 INDICATE THE USE OF DRYWALL DROPED CEILING PANELS |
| WITH LATTICE, A NOTE ON A-3 INDICATES METHOD OF |
| ATTACHMENT, SUSPENSION BY OTHERS, THIS SYSTEM TO BE |
| REVIEWED BY THE DESIGN PROFESSIONAL, IT CAN BE |
| PERMITTED UNDER THIS PERMIT OR COME IN AS A STAND ALONE |
| PERMIT. THE DROPPED CEILING WILL NEED TO SHOW |
| COMPLIANCE WITH |
| 803.3 & 803.4.1 AND MEET THE FINISH REQUIREMENTS OF |
| TABLE 803.5. |
| |
| 14-15) COMPLIED. |
| |
| 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |