Plan Review Notes
Plan Review Notes For Permit 11100370
Permit Number 11100370
Review Stop B
Sequence Number 2
Notes
Date Text
2012-01-06 09:51:34BUILDING PLAN REVIEW
 PERMIT: 11100370
 ADD: 215 CLEMATIS ST
 CONT: L B DEVELOPMENT
 TEL: (954)709-1926
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 01/06/2012
 2ND REVIEW
 ACTION: DENIED
  
 1) THE MEZZANINE AND KITCHEN BELOW MUST MAINTAIN A
 FINISHED CEILING HEIGHT OF 7'-0" FBC-B 1208.2 EXCEPTION
 # 3. SHEET A-3 STILL INDICATES A 6'-8" DIMENSION.
  
 2) NO FIRE SPRINKLER PLANS WERE SUBMITTED. THE LAST
 KNOWN USE OF THIS SPACE WAS A DRESS SHOP MAKING THIS A
 CHANGE OF OCCUPANCY. THE 2007/09 FBC EXISTING BUILDING
 CODE CHAPTER 9 CHANGE OF OCCUPANCY SECTION EXST BLDG
 COE 904.1 . FIRE PROTECTION REQUIREMENTS OF SECTION 912
 SHALL APPLY WHERE A BUILDING OR PORTIONS THEREOF
 UNDERGO A CHANGE OF OCCUPANCY CLASSIFICATION.
  
 EXST BLDG CODE 912.2 FIRE PROTECTION SYSTEMS. FIRE
 PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH
 SECTIONS 912.2.1 AND 912.2.2.
  
 2A) EXST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. WHERE
 A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2007/09 FBC-B 903.2 WHERE REQUIRED. APPROVED AUTOMATIC
 SPRINKLER SYSTEMS IN NEW BUILDINGS AND STRUCTURES SHALL
 BE PROVIDED IN THE LOCATIONS DESCRIBED IN THIS SECTION.
 FBC-B 903.2.1.2 GROUP A-2. AN AUTOMATIC SPRINKLER
 SYSTEM SHALL BE PROVIDED FOR GROUP A-2 OCCUPANCIES
 WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2).
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE.
 3. THE FIRE AREA IS LOCATED ON A FLOOR OTHER THAN THE
 LEVEL OF EXIT DISCHARGE.
 4. NIGHTCLUBS OR SIMILAR USAGE WHEN OCCUPANT LOAD IS
 100 OR MORE.
 903.3 INSTALLATION REQUIREMENTS. AUTOMATIC SPRINKLER
 SYSTEMS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH SECTIONS 903.3.1 THROUGH 903.3.7.
 903.4 SPRINKLER SYSTEM MONITORING AND ALARMS. ALL
 VALVES CONTROLLING THE WATER SUPPLY FOR AUTOMATIC
 SPRINKLER SYSTEMS, PUMPS, TANKS, WATER LEVELS AND
 TEMPERATURES, CRITICAL AIR PRESSURES AND WATER-FLOW
 SWITCHES ON ALL SPRINKLER SYSTEMS SHALL BE ELECTRICALLY
 SUPERVISED IN ACCORDANCE WITH NFPA 72.
 903.4.1 SIGNALS. ALARM, SUPERVISORY AND TROUBLE SIGNALS
 SHALL BE DISTINCTLY DIFFERENT AND AUTOMATICALLY
 TRANSMITTED TO AN APPROVED CENTRAL STATION, REMOTE
 SUPERVISING STATION OR PROPRIETARY SUPERVISING STATION
 AS DEFINED IN NFPA 72 OR, WHEN APPROVED BY THE FIRE
 CODE OFFICIAL, SHALL SOUND AN AUDIBLE SIGNAL AT A
 CONSTANTLY ATTENDED LOCATION.
  
  
 2B) COMPLIED. FIRE ALAARM PLAANS WERE SUBMITTED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) MISSING PRODUCT APPROVALS FBC-B 1609 COMPONENTS &
 CLADDING, RULE 9N-3.
 5A-B) COMPLIED.
 5C) EXTERIER WALK IN COOLERS &/FREEZERS
  
 6-12) COMPLIED.
  
 13) PROVISO: A SEPERATE PREMIT IS REQUIRED. SHEET A-3 &
 A-4 INDICATE THE USE OF DRYWALL DROPED CEILING PANELS
 WITH LATTICE, A NOTE ON A-3 INDICATES METHOD OF
 ATTACHMENT, SUSPENSION BY OTHERS, THIS SYSTEM TO BE
 REVIEWED BY THE DESIGN PROFESSIONAL, IT CAN BE
 PERMITTED UNDER THIS PERMIT OR COME IN AS A STAND ALONE
 PERMIT. THE DROPPED CEILING WILL NEED TO SHOW
 COMPLIANCE WITH
 803.3 & 803.4.1 AND MEET THE FINISH REQUIREMENTS OF
 TABLE 803.5.
  
 14-15) COMPLIED.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  