Plan Review Notes
Plan Review Notes For Permit 11100370
Permit Number 11100370
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-10-20 13:01:00215 CLEMATIS STREET
 PERMIT #11100370
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: THIS IS A CHANGE OF OCCUPANCY FROM MERCANTILE TO
 ASSEMBLY.
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 STRUCTURES WITH LIGHT FRAME FLOOR TRUSS CONSTRUCTION
 SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE
 BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER "F" DESIGNATION
 PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE
 CODE 69A-60.0081.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 VERIFY NO OTHER LOCKS OR LATCHES ARE INSTALLED ON THE
 EXISTING EXIT DOORS WITH PANIC HARDWARE.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE STAIR AND HANDRAIL DETAILS.
  
 INTERIOR WALL AND CEILING FINISHES SHALL MEET AT LEAST
 A CLASS C RATING FOR FLAME SPREAD AND SMOKE
 DEVELOPEMENT.
  
 SHEET A-2: INDICATE THE LOCATIONS OF WHEELCHAIR
 SEATING.
  
 SHEET A-2 (DOOR #2 AND #6): DURING ITS SWING, ANY DOOR
 IN A MEANS OF EGRESS SHALL PROJECT NOT MORE THAN
 7-INCHES INTO THE REQUIRED WIDTH OF THE EGRESS PATH
 WHEN FULLY OPEN.
  
 SHEET A-4: HEADROOM SHALL BE NOT LESS THAN 7'-6" WITH
 PROJECTIONS FROM THE CEILING NOT LESS THAN 6'-8" ABOVE
 THE FLOOR. THE MINIMUM CEILING HEIGHT SHALL BE
 MAINTAINED FOR NOT LESS THAN TWO-THIRDS OF THE CEILING
 AREA OF ANY ROOM OR SPACE.
  
 SHEET FS-1.0: DEEP FAT FRYERS SHALL BE EQUIPPED WITH A
 SEPARATE HIGH-LIMIT CONTROL IN ADDITION TO THE
 ADJUSTABLE THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN
 THE FAT TEMPERATURE REACHES 475F DEGREES AT 1 INCH
 BELOW THE SURFACE.
  
 SHEET FS-1.0: PROVIDE AN 8? TALL STEEL BAFFLE OR
 PROVIDE 16? OF SPACE BETWEEN THE DEEP FAT FRYER AND
 SURFACE FLAMES OF THE ADJACENT EQUIPMENT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  