2011-10-20 13:01:00 | 215 CLEMATIS STREET |
| PERMIT #11100370 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NOTE: THIS IS A CHANGE OF OCCUPANCY FROM MERCANTILE TO |
| ASSEMBLY. |
| |
| ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. |
| |
| STRUCTURES WITH LIGHT FRAME FLOOR TRUSS CONSTRUCTION |
| SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO THE |
| BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| REFLECTIVE COLOR AND BEAR THE LETTER "F" DESIGNATION |
| PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE |
| CODE 69A-60.0081. |
| |
| PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| CONTRAST THE BACKGROUND |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| VERIFY NO OTHER LOCKS OR LATCHES ARE INSTALLED ON THE |
| EXISTING EXIT DOORS WITH PANIC HARDWARE. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| PROVIDE STAIR AND HANDRAIL DETAILS. |
| |
| INTERIOR WALL AND CEILING FINISHES SHALL MEET AT LEAST |
| A CLASS C RATING FOR FLAME SPREAD AND SMOKE |
| DEVELOPEMENT. |
| |
| SHEET A-2: INDICATE THE LOCATIONS OF WHEELCHAIR |
| SEATING. |
| |
| SHEET A-2 (DOOR #2 AND #6): DURING ITS SWING, ANY DOOR |
| IN A MEANS OF EGRESS SHALL PROJECT NOT MORE THAN |
| 7-INCHES INTO THE REQUIRED WIDTH OF THE EGRESS PATH |
| WHEN FULLY OPEN. |
| |
| SHEET A-4: HEADROOM SHALL BE NOT LESS THAN 7'-6" WITH |
| PROJECTIONS FROM THE CEILING NOT LESS THAN 6'-8" ABOVE |
| THE FLOOR. THE MINIMUM CEILING HEIGHT SHALL BE |
| MAINTAINED FOR NOT LESS THAN TWO-THIRDS OF THE CEILING |
| AREA OF ANY ROOM OR SPACE. |
| |
| SHEET FS-1.0: DEEP FAT FRYERS SHALL BE EQUIPPED WITH A |
| SEPARATE HIGH-LIMIT CONTROL IN ADDITION TO THE |
| ADJUSTABLE THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN |
| THE FAT TEMPERATURE REACHES 475F DEGREES AT 1 INCH |
| BELOW THE SURFACE. |
| |
| SHEET FS-1.0: PROVIDE AN 8? TALL STEEL BAFFLE OR |
| PROVIDE 16? OF SPACE BETWEEN THE DEEP FAT FRYER AND |
| SURFACE FLAMES OF THE ADJACENT EQUIPMENT. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |
| |