Plan Review Notes
Plan Review Notes For Permit 11100267
Permit Number 11100267
Review Stop B
Sequence Number 1
Notes
Date Text
2011-10-20 16:20:30****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE INFORMATION REGARDING OCCUPANCY
 CLASSIFICATION. PLEASE ALSO SEE THE FOLLOWING CODE
 SECTIONS:
  
 FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF
 EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE
 INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS
 OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH
 OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY
 THIS CHAPTER.
  
 1008.1.3.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S,
 HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE
 PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM
 THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL
 KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS
 OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE
 FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY
 THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS
 ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR
 EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL
 SLIDING OR VERTICAL SECURITY GRILLES.
  
 NOTE THAT THERE IS NO PROVISION FOR BLOCKING EXITS WITH
 HURRICANE PROTECTION FOR ANY OCCUPANCY OTHER THAN GROUP
 R, SEE FBC 1008.1.3.6.
  
 PLEASE EITHER REMOVE ALL DOORS FROM SCOPE OF WORK OR
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC CHAPTER 10.
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS OR TO EMAIL
 ADDITIONAL INFORMATION.
  
 2. PLEASE INCLUDE SPANS IN THE INSTALLATION SCHEDULE.
 FOR INSTANCE, A 96" OPENING WITH A 3" TOP AND BOTTOM
 EDGE DISTANCE WOULD HAVE A SPAN OF 102". REVISE ANCHOR
 SPACING IF NECESSARY.
  
 3. PLEASE EITHER REVISE HORIZONTAL OPENINGS TO A BLOCK
 SUBSTRATE OR PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THE SIDES OF THE WINDOW OPENINGS ARE
 CONCRETE. CBS STRUCTURES TYPICALLY HAVE EITHER HOLLOW
 OR FILLED CELLS AT THE OPENINGS, NOT FORMED AND POURED
 COLUMNS. REVISE ANCHOR SPACING IF NECESSARY.
  