Plan Review Notes For Permit 11100235 |
Permit Number |
11100235 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-11-03 12:18:27 | 777 SOUTH FLAGLER DRIVE - EAST TOWER PENTHOUSE | | PERMIT #11100235 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE LIFE SAFETY PLAN INDICATES AN OCCUPANT LOAD OF 399 | | PERSONS. USING A CAPACITY FACTOR OF 0.2 INCHES OF WIDTH | | PER PERSON FOR LEVEL COMPONENTS, THE TWO EXIT STAIR | | DOORS WOULD NEED A TOTAL CLEAR WIDTH OF 80 INCHES (399 | | X 0.2 = 80). ONLY 69 INCHES OF EXIT STAIR WIDTH IS | | PROVIDED. | | | | INDICATE IF THE BALCONY DOORS WILL BE EQUIPPED WITH ANY | | LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A | | LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE | | RELEASED FROM THE EGRESS SIDE OF THE DOOR. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW |
|