2011-11-03 12:18:27777 SOUTH FLAGLER DRIVE - EAST TOWER PENTHOUSE
 PERMIT #11100235
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE LIFE SAFETY PLAN INDICATES AN OCCUPANT LOAD OF 399
 PERSONS. USING A CAPACITY FACTOR OF 0.2 INCHES OF WIDTH
 PER PERSON FOR LEVEL COMPONENTS, THE TWO EXIT STAIR
 DOORS WOULD NEED A TOTAL CLEAR WIDTH OF 80 INCHES (399
 X 0.2 = 80). ONLY 69 INCHES OF EXIT STAIR WIDTH IS
 PROVIDED.
  
 INDICATE IF THE BALCONY DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW