2011-10-19 13:21:43 | 777 SOUTH FLAGLER DRIVE - EAST TOWER PENTHOUSE |
| PERMIT #11100235 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NO ADDRESS PROVIDED ON DRAWINGS. |
| |
| PROVIDE A LIFE SAFETY PLAN SHOWING THE OCCUPANT LOADS, |
| EXIT STAIR LOCATIONS, STAIR DOOR CAPACITY AND TRAVEL |
| DISTANCES FOR THE ENTIRE FLOOR. THIS FLOOR APPEARS TO |
| HAVE TWO EXIT STAIRS. ADDING A BALCONY ASSEMBLY AREA |
| WITH 50+ OCCUPANTS MAY EXCEED THE CURRENT EXIT CAPACITY |
| OF THIS FLOOR. |
| |
| INDICATE THE ADA SEATING LOCATIONS. |
| |
| THE WIDTH OF AISLES SERVING SEATING AT TABLES SHALL BE |
| NOT LESS THAN 44-INCHES WHERE SERVING AN OCCUPANT LOAD |
| EXCEEDING 50; OR 36-INCHES WHERE SERVING AN OCCUPANT |
| LOAD OF 50 OR FEWER. |
| |
| DOORS SERVING 50 OR MORE PERSONS SHALL SWING IN THE |
| DIRECTION OF EGRESS. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| INDICATE THE DOOR HARDWARE. THE RELEASING MECHANISM ON |
| ALL DOORS SHALL OPEN THE DOOR WITH NOT MORE THAN ONE |
| RELEASING OPERATION. THE RELEASING MECHANISM SHALL HAVE |
| AN OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED |
| UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE |
| SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND |
| SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR |
| TWISTING OF THE WRIST TO OPERATE. |
| |
| INDICATE LOCATIONS OF NEAREST EXISTING PORTABLE FIRE |
| EXTINGUISHERS. TRAVEL DISTANCE TO EXTINGUISHERS SHALL |
| NOT EXCEED 75 FEET. |
| |
| TWO FIRE ALARM SPEAKER/STROBES WILL NOT ADEQUATELY |
| COVER THE ENTIRE BALCONY AREA. |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| MODIFICATION OF THE FIRE ALARM SYSTEM. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |
| |