Plan Review Notes For Permit 11100193 |
Permit Number |
11100193 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-10-18 10:30:55 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. THE DOOR PRODUCT APPROVALS ARE EXPIRED. PLEASE | | PROVIDE CURRENT PRODUCT APPROVALS FAC9N-3. | | | | 2. DOOR PRODUCT APPROVAL TO BE REVIEWED BY DESIGNER OF | | RECORD, FBC 106.3.3. | | | | 3. A SEPARATE PERMIT FOR EACH BUILDING IS REQUIRED. IT | | APPEARS FROM THE SITE PLAN THAT THERE ARE FOUR | | BUILDINGS. SUBMIT THREE ADDITIONAL PERMIT APPLICATIONS | | WITH THE CORRECT ADDRESS ON EACH. IF ALL FOUR BUILDINGS | | HAVE THE SAME STREET ADDRESS, DIFFERENTIATE BY | | INCLUDING THE UNIT NUMBERS IN THE APPLICATION | | DESCRIPTION. | | | | 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. | | |
|