Plan Review Notes
Plan Review Notes For Permit 11100164
Permit Number 11100164
Review Stop B
Sequence Number 2
Notes
Date Text
2011-11-30 15:48:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. PROVIDE INFORMATION REGARDING THE LOCATION OF THE
 ACCESSIBLE ENTRANCE(S), FBC11 4.3.2, FBC 11 4.
  
 2. FBC 11 4.3.2, SHOW ACCESSIBLE ROUTE FROM THE PUBLIC
 WAY TO THE ACCESSIBLE BUILDING ENTRANCE.
  
 3. OK
  
 4. FBC 11 4.6.2, ACCESSIBLE PARKING SPACES SERVING A
 PARTICULAR BUILDING SHALL BE LOCATED ON THE SHORTEST
 SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE.
  
 2ND REVIEW, PLEASE SHOW THE ACCESSIBLE ENTRANCES.
 PROXIMITY OF THE ACCESSIBLE SPACES TO THE ENTRANCE(S)
 CANNOT BE DETERMINED. IF THERE IS MORE THAN ONE
 ADJACENT PARKING AREA, ACCESSIBLE PARKING IS TO BE
 DISPERSED.
  
 5. ADVISORY ONLY, THE FOLLOWING WEBSITE MAY BE
 INFORMATIVE:
 HTTP://WWW.ADA.GOV/RESTRIPE.PDF
  
 PLEASE NOTE THAT ADA AND THE FLORIDA BUILDING CODE
 CONSIDERS RESTRIPING "NEW CONSTRUCTION."
  
 6. THE DESIGNER TAKING RESPONSIBILITY FOR THIS DESIGN
 AND INFORMATION (AND CERTIFYING AS TO CODE COMPLIANCE)
 IS TO PROVIDE HIS/HER NAME AND SIGNATURE ON THE PLAN.
  
 2ND REVIEW, IT APPEARS THAT THE CONTRACTOR HAS REVISED
 THE ENGINEER'S SEALED PLAN. IF THE CONTRACTOR IS TAKING
 RESPONSIBILITY FOR THE DESIGN, PLEASE PROVIDE PRINTED
 NAME, SIGNATURE, AND LICENSE NUMBER ON THE PLAN.
  
 7. PLEASE REVISE PLAN TO INCLUDE TOTAL NUMBER OF
 PARKING SPACES AND NUMBER OF ACCESSIBLE SPACES, FBC
 11-4.
  
 SEE FBC 11-4.1.2(5)(A), FOUR SPACES REQUIRED, THREE
 SHOWN.
  
 PLEASE NOTE THAT THE ENGINEER IS IN CONVERSATIONS WITH
 PLANS EXAMINER IN ORDER TO RESOLVE OUTSTANDING DESIGN
 ISSUES.
  
  
  
  