Date |
Text |
2011-11-16 12:13:45 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| 1. PROVIDE INFORMATION REGARDING THE LOCATION OF THE |
| ACCESSIBLE ENTRANCE(S), FBC11 4.3.2, FBC 11 4. |
| |
| 2. FBC 11 4.3.2, SHOW ACCESSIBLE ROUTE FROM THE PUBLIC |
| WAY TO THE ACCESSIBLE BUILDING ENTRANCE. |
| |
| 3. ACCESSIBLE PARKING IS TO COMPLY WITH FBC 11 |
| 4.6.2(1), TO BE LOCATED ON AN ACCESSIBLE ROUTE NO LESS |
| THAN 44 INCHES WIDE SO THAT USERS WILL NOT BE COMPELLED |
| TO WALK OR WHEEL BEHIND PARKED VEHICLES. THE PLAN IS |
| NOT CLEAR AS TO LOCATION OF ACCESS AISLES AND RAMPS OR |
| CURB RAMPS, IF ANY. |
| |
| 4. FBC 11 4.6.2, ACCESSIBLE PARKING SPACES SERVING A |
| PARTICULAR BUILDING SHALL BE LOCATED ON THE SHORTEST |
| SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING |
| TO AN ACCESSIBLE ENTRANCE. |
| |
| 5. ADVISORY ONLY, THE FOLLOWING WEBSITE MAY BE |
| INFORMATIVE: |
| HTTP://WWW.ADA.GOV/RESTRIPE.PDF |
| |
| PLEASE NOTE THAT ADA AND THE FLORIDA BUILDING CODE |
| CONSIDERS RESTRIPING "NEW CONSTRUCTION." |
| |
| 6. THE DESIGNER TAKING RESPONSIBILITY FOR THIS DESIGN |
| AND INFORMATION (AND CERTIFYING AS TO CODE COMPLIANCE) |
| IS TO PROVIDE HIS/HER NAME AND SIGNATURE ON THE PLAN. |
| |
| 7. PLEASE REVISE PLAN TO INCLUDE TOTAL NUMBER OF |
| PARKING SPACES AND NUMBER OF ACCESSIBLE SPACES, FBC |
| 11-4. |
| |
| |
| |