2011-10-04 14:15:32 | BUILDING REVISION CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- ENGINEER TO REVISE THE ATTACHMENT REQUIREMENTS FOR | | ROOF IN THE FIELD AREA (ROOF ZONE #1). ACCORDING TO THE | | NOA SUBMITTED THE BASE SHEET FASTENING OPTION #3 STATES | | TWO ROWS IN THE FIELD AT 9"O.C. ENGINEER STATES TWO | | ROWS AT 12" O.C. REVISE AS REQUIRED. DESIGN PRESSURES | | SHOWN ON THE NOA ARE APPLICABLE TO THE FIELD OF THE | | ROOF AREA (ROOF ZONE #1). SEE SEC. 8.1 OF RAS 117 | | CALCULATIONS. | | | | 2- ENGINEER NEEDS TO REVISE THE FASTENER SPACING FOR | | THE PERIMETER AND CORNER AREAS. ACCORDING TO SEC. 10 OF | | THE RAS 117 CALCULATIONS ALL FRACTIONS SHALL BE ROUNDED | | DOWN TO THE NEXT WHOLE NUMBER. REVISE AS REQUIRED. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|