2011-10-14 12:41:37 | BUILDING PLAN REVIEW |
| PERMIT: 110908259 (REV) / 11080026 (PER) |
| ADD: 1901 N FLAGLER |
| CONT: IBIS BUILD. CORP. |
| TEL: (561)568-2570 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| BUILDING PROVISO: |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. CONTRACTOR |
| CONTINUING WORK AT OWN RISK! |
| |
| 1) SHEET A3.1 DETAIL 03 (NEW SHEET/ NEW WORK) |
| 1A) MISSING PRODUCT APPROVALS NEW SOLAR INOVATIONS INC |
| OUTFOLDING SERIES 5000 ST. ALUM DOOR SYSTEMS |
| 1B) MISSING PRODUCT APPROVAL FOR NEW ALUMINUM |
| STOREFRONT DOORS. |
| 1C) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 2) NEW WORK SHEET A5.6 |
| 2A) MISSING PRODUCT APPROVAL FOR 42" X 42" ACCESS DOOR. |
| 2B) PRE-MANUFACTURED STANDING SEAM METAL ROOFING |
| 2C) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 3) S-2.1 MISSING WIND DESIGN CRITERIA FOR THE NEW |
| SLOPED ROOF, NO PRESSURES FOR ROOF ZONES SLOPED ROOF |
| 8/12 PITCH. |
| |
| JAMES A. WITMER CBO |