2011-10-03 14:18:34 | BUILDING PLAN REVIEW |
| PERMIT: 11090808 |
| ADD: 501 N OLIVE AVE |
| CONT: A & C PAVERS INC |
| TEL: (561)201-0585 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1A) SHEET A2.3 THE SOUTH END OF THE SHEET INDICATES A |
| RAMP AND A 6'-0"X6'-0" TREE GRATE, PLEASE PROVIDE |
| DOCUMENTATION THAT THE TREE GRATE WILL NOT OBSTRUCT THE |
| 60" X 60" MINIMUM LANDING SIZE FOR LANDINGS WITH CHANGE |
| OF DIRECTION ( 11-4.8.4(3). |
| THE SECOND ISSUE WOULD BE THE SLOTS IN THE GRATE SIZE |
| OF SLOT AND DIRECTION OF SLOT VERSES THE DIRECTION OF |
| TRAVEL. |
| 11-4.5.4 GRATINGS. IF GRATINGS ARE LOCATED IN WALKING |
| SURFACES, THEN THEY SHALL HAVE SPACES NO GREATER THAN |
| 1/2 INCH (13 MM) WIDE IN ONE DIRECTION [SEE FIGURE |
| 8(G)]. IF GRATINGS HAVE ELONGATED OPENINGS, THEN THEY |
| SHALL BE PLACED SO THAT THE LONG DIMENSION IS |
| PERPENDICULAR TO THE DOMINANT DIRECTION OF TRAVEL [SEE |
| FIGURE 8(H)]. |
| |
| 1B) PLEASE PROVIDE THE SLOPE OF THE RAMPS WHEN |
| FINISHED. 11-4.8.2 |
| |
| 2) ALONG THE FRONT OF THE BUILDING THERE IS 6 AREAS |
| WHERE THERE IS APPROXIMATELY 2'-0" FROM THE FACE OF THE |
| BUILDING TO THE TREE GRATE, THIS IS THE ACCESSABLE PATH |
| TO THE BUILDING ENTRY, PLEASE PROVIDE COMPLIANCE WITH; |
| 11-4.5.4 GRATINGS. IF GRATINGS ARE LOCATED IN WALKING |
| SURFACES, THEN THEY SHALL HAVE SPACES NO GREATER THAN |
| 1/2 INCH (13 MM) WIDE IN ONE DIRECTION [SEE FIGURE |
| 8(G)]. IF GRATINGS HAVE ELONGATED OPENINGS, THEN THEY |
| SHALL BE PLACED SO THAT THE LONG DIMENSION IS |
| PERPENDICULAR TO THE DOMINANT DIRECTION OF TRAVEL [SEE |
| FIGURE 8(H)]. |
| |
| 3) PLEASE PROVIDE THE CROSS SLOPE OF RAMPS, LANDINGS |
| AND WALKWAYS.11-4.3.7. |
| |