Plan Review Notes For Permit 11090790 |
Permit Number |
11090790 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2011-10-12 16:38:29 | REROOF BUILDING REVIEW FIFTH CHECKLIST. | | | | 1- NEW ENGINEER PROVIDING THE RAS 117 CALCULATIONS: | | A) CALCULATIONS SUBMITTED SPECIFY INSULATED SYSTEM ON | | PAGE 8 AND 9 OF NOA 07-1203.01. CONTRACTOR SAID HE'S | | INSTALLING A NON-INSULATED SYSTEM. REVISE AS REQUIRED. | | | | B) NOA 07-1203.01 SPECIFIED BY THE ENGINEER WAS | | SUPERSEDED BY MIAMI-DADE. NEED TO USE CURRENT NOA. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|