Plan Review Notes For Permit 11090790 |
Permit Number |
11090790 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2011-10-11 11:20:52 | RE-ROOF BUILDING REVIEW FOURTH CHECKLIST: | | | | ARCHITECT TO REVISE RAS 117 CALCULATIONS SUBMITTED: | | | | 1- OK. | | | | 2- OK. | | | | 3- OK. | | | | 4- OK. | | | | 5- THE DESIGN PRESSURES LISTED ON THE NOA IS APPLICABLE | | FOR THE FIELD OF THE ROOF (ZONE 1). SEE SEC. 8.1 OF RAS | | 117 CALCULATIONS. SPACING SHOWN FOR THE PERIMETER AREA | | IS INCORRECT. | | | | | | ***RESPONSE: NOT ADDRESSED CORRECTLY. | | | | 6- NAIL SPACING FOR CORNER AREAS IS INCORRECT. REVISE | | CALCULATIONS AS REQUIRED. | | | | | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|