Plan Review Notes
Plan Review Notes For Permit 11090790
Permit Number 11090790
Review Stop B
Sequence Number 4
Notes
Date Text
2011-10-11 11:20:52RE-ROOF BUILDING REVIEW FOURTH CHECKLIST:
  
 ARCHITECT TO REVISE RAS 117 CALCULATIONS SUBMITTED:
  
 1- OK.
  
 2- OK.
  
 3- OK.
  
 4- OK.
  
 5- THE DESIGN PRESSURES LISTED ON THE NOA IS APPLICABLE
 FOR THE FIELD OF THE ROOF (ZONE 1). SEE SEC. 8.1 OF RAS
 117 CALCULATIONS. SPACING SHOWN FOR THE PERIMETER AREA
 IS INCORRECT.
  
  
 ***RESPONSE: NOT ADDRESSED CORRECTLY.
  
 6- NAIL SPACING FOR CORNER AREAS IS INCORRECT. REVISE
 CALCULATIONS AS REQUIRED.
  
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712