Plan Review Notes
Plan Review Notes For Permit 11090790
Permit Number 11090790
Review Stop B
Sequence Number 3
Notes
Date Text
2011-10-07 16:32:11RE-ROOF BUILDING REVIEW THIRD CHECKLIST:
  
 ARCHITECT TO REVISE RAS 117 CALCULATIONS SUBMITTED:
  
 1- ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". (THIS WAS
 REQUESTED ON FIRS CHECKLIST). ARCHITECT NEED TO REVISE
 CALCULATIONS USING THE DESIGN PRESSURES FOR EXPOSURE
 "B".
  
 ***RESPONSE: NOT ADDRESSED. ARCHITECT IS STILL USING
 DESIGN PRESSURES FOR EXPOSURE "B".
  
 2- OK.
  
 3- CONTRACTOR SAID USING ASSEMBLY WITH RING SHANK NAILS
 NOT SCREWS. PROVIDE CALCULATIONS USING THE CORRECT
 APPROVED ASSEMBLY.
  
 ***RESPONSE:. NOT ADDRESSED CORECTLY.
  
 4- FASTENER SPACING NEED TO BE ROUNDED DOWN TO THE NEXT
 WHOLE NUMBER NOT ROUNDED UP. SEE SEC. 10.4.5 OF RAS 117
 CALCULATIONS. REVISE FASTENER SPACING FOR PERIMETER AND
 CORNER
 AREAS.
  
 ***RESPONSE: NOT ADDRESSED CORRECTLY.
  
 5- THE DESIGN PRESSURES LISTED ON THE NOA IS APPLICABLE
 FOR THE FIELD OF THE ROOF (ZONE 1). SEE SEC. 8.1 OF RAS
 117 CALCULATIONS. SPACING SHOWN FOR THE PERIMETER AREA
 IS INCORRECT.
  
  
 ***RESPONSE: NOT ADDRESSED CORRECTLY.
  
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712