Plan Review Notes For Permit 11090790 |
Permit Number |
11090790 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-10-06 16:15:05 | RE-ROOF BUILDING REVIEW SECOND CHECKLIST: | | | | ARCHITECT TO REVISE RAS 117 CALCULATIONS SUBMITTED: | | | | 1- ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 THIS | | BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". (THIS WAS | | REQUESTED ON FIRS CHECKLIST). ARCHITECT NEED TO REVISE | | CALCULATIONS USING THE DESIGN PRESSURES FOR EXPOSURE | | "B". | | | | 2- ARCHITECT TO REVIEW NOA SUBMITTED. THE WIDTH OF THE | | ANCHOR BASE SHEET IS NOT 36". SEE NOA AND REVISE | | CALCULATIONS AS REQUIRED. | | | | 3- CONTRACTOR SAID USING ASSEMBLY WITH RING SHANK NAILS | | NOT SCREWS. PROVIDE CALCULATIONS USING THE CORRECT | | APPROVED ASSEMBLY. | | | | 4- FASTENER SPACING NEED TO BE ROUNDED DOWN TO THE NEXT | | WHOLE NUMBER NOT ROUNDED UP. SEE SEC. 10.4.5 OF RAS 117 | | CALCULATIONS. REVISE FASTENER SPACING FOR PERIMETER AND | | CORNER AREAS. | | | | 5- THE DESIGN PRESSURES LISTED ON THE NOA IS APPLICABLE | | FOR THE FIELD OF THE ROOF (ZONE 1). SEE SEC. 8.1 OF RAS | | 117 CALCULATIONS. SPACING SHOWN FOR THE PERIMETER AREA | | IS INCORRECT. | | | | | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|