2011-10-06 16:15:05RE-ROOF BUILDING REVIEW SECOND CHECKLIST:
  
 ARCHITECT TO REVISE RAS 117 CALCULATIONS SUBMITTED:
  
 1- ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". (THIS WAS
 REQUESTED ON FIRS CHECKLIST). ARCHITECT NEED TO REVISE
 CALCULATIONS USING THE DESIGN PRESSURES FOR EXPOSURE
 "B".
  
 2- ARCHITECT TO REVIEW NOA SUBMITTED. THE WIDTH OF THE
 ANCHOR BASE SHEET IS NOT 36". SEE NOA AND REVISE
 CALCULATIONS AS REQUIRED.
  
 3- CONTRACTOR SAID USING ASSEMBLY WITH RING SHANK NAILS
 NOT SCREWS. PROVIDE CALCULATIONS USING THE CORRECT
 APPROVED ASSEMBLY.
  
 4- FASTENER SPACING NEED TO BE ROUNDED DOWN TO THE NEXT
 WHOLE NUMBER NOT ROUNDED UP. SEE SEC. 10.4.5 OF RAS 117
 CALCULATIONS. REVISE FASTENER SPACING FOR PERIMETER AND
 CORNER AREAS.
  
 5- THE DESIGN PRESSURES LISTED ON THE NOA IS APPLICABLE
 FOR THE FIELD OF THE ROOF (ZONE 1). SEE SEC. 8.1 OF RAS
 117 CALCULATIONS. SPACING SHOWN FOR THE PERIMETER AREA
 IS INCORRECT.
  
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER