Date Text
2011-09-29 15:48:591507 BELVEDERE ROAD
 PERMIT #11090779
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 IN ADDITION TO TAMPER SWITCHES, PROVIDE CHAIN WITH LOCK
 FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PER LOCAL POLICY, FIRE DEPARTMENT CONNECTIONS SHALL
 HAVE A SIAMESE CONNECTION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 INDICATE THE METHOD USED TO SUPPORT THE BACKFLOW
 PREVENTOR.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION AND MAIN SPRINKLER CONTROL VALVE.
  
 THE SPRINKLER SPRAY IS OBSTRUCTED BY THE SOFFIT
 (6-INCHES LOWER) IN LARGE CONFERENCE ROOM #102.
  
 THE ONLY SPRINKLER PIPING PERMITTED IN THE ELECTRICAL
 ROOM IS THE BRANCH LINE SUPPLYING THE SPRINKLER.
 RELOCATE THE INSPECTOR'S TEST CONNECTION.
  
 THE HYDRAULIC AREA FOR DESIGN AREA #1 SHALL BE AT LEAST
 36 FEET LONG WHEN USING 1.2 MULTIPLIED BY 900 SQUARE
 FEET.
  
 PROVIDE A SECTION DETAIL INDICATING THE SPRINKLER
 LOCATIONS IN THE COMBUSTIBLE CONCEALED ROOF SPACE WITH
 REGARDS TO THE SLOPED ROOF FRAMING MEMBERS.
  
 PROVIDE HYDRAULIC CALCULATIONS FOR THE SPRINKLERS
 PROTECTING THE COMBUSTIBLE CONCEALED SPACE. THE SYSTEM
 AREA OF OPERATION SHALL BE INCREASED BY 30 PERCENT WHEN
 THE CEILING PITCH EXCEEDS ONE IN SIX.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  