2011-09-29 12:31:42303 EVERNIA STREET
 PERMIT #11090673
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE ALARM NOTE #2 INDICATES ALL STROBE APPLIANCES TO
 BE AT LEAST 75 CANDELA. INDICATE THE CANDELA RATING FOR
 THE HORN/STROBE APPLIANCES SHOWN IN SUITE 101 THROUGH
 SUITE 104 AS THE DISTANCE FROM WALL TO WALL APPEARS TO
 BE ROUGHLY 55 FEET.
  
 ELEVATOR RECALL SHALL BE INTERFACED WITH FIRE ALARM
 SYSTEM.
  
 PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW
 SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO
 THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER
 ACTIVATES IN THE ELEVATOR MACHINE ROOM.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 VOLTAGE DROP AND BATTERY CALCULATIONS NOT SIGNED/SEALED
 BY PROFESSIONAL ENGINEER.
  
 THE FIRE SPRINKLER FLOW SWITCHES AND TAMPER SWITCHES DO
 NOT APPEAR TO BE MONITORED BY THE FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  