Plan Review Notes For Permit 11090634 |
Permit Number |
11090634 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-09-27 11:56:44 | 777 SOUTH FLAGLER DRIVE - SUITE #1600W | | PERMIT #11090634 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO - SUBMIT REVISION***** | | | | PROVIDE SUITE NUMBER ON PLANS. | | | | FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND | | END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE | | PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE | | LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE | | THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING | | UPWARD MOVEMENT. MODIFY HANGER LOCATION DETAIL TO | | ACCOUNT FOR SYSTEM PRESSURES ABOVE 100 PSI. | | | | INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE FOR THIS | | FLOOR. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|