 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 PROVIDE SUITE NUMBER ON PLANS.
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT. MODIFY HANGER LOCATION DETAIL TO
 ACCOUNT FOR SYSTEM PRESSURES ABOVE 100 PSI.
  
 INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE FOR THIS
 FLOOR.
  