2011-09-22 12:30:44 | 801 SOUTH OLIVE AVENUE - UNITS #806/#807 | | PERMIT #11090473 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | ELIMINATE ALL SHEET REFERENCES TO NFPA 13R AS THIS | | STANDARD CAN ONLY BE UTILIZED FOR RESIDENTIAL BUILDINGS | | UP TO FOUR STORIES IN HEIGHT. SPRINKLER DESIGN SHALL | | CONFORM TO NFPA 13 WITH THE USE OF RESIDENTIAL | | SPRINKLERS WITHIN DWELLING UNITS. | | | | SPRINKLER PROTECTION IS REQUIRED IN ALL CLOSET SPACES. | | THE EXCEPTION TO NOT LOCATE SPRINKLERS IN SMALL CLOSETS | | 24 SQUARE FEET OR SMALLER ONLY PERTAINS TO HOTEL/MOTEL | | OCCUPANCIES. | | | | THE DISTANCE BETWEEN TWO PENDENT SPRINKLERS IN THE | | LIVING/SALON ROOM EXCEEDS 18 FEET. | | | | SPRINKLER COVERAGE APPEARS INADEQUATE BETWEEN THE | | FAMILY KITCHEN AND PANTRY DOOR AREA. | | | | PROVIDE CEILING AND SOFFIT HEIGHTS ON PLANS. | | | | THE HANGER SPACING CHART SHOWS DISTANCES FOR SYSTEM | | PRESSURES LESS THAN 100 PSI. REVISE CHART FOR SYSTEM | | PRESSURE EXCEEDING 100 PSI. | | | | INDICATE THE METHOD TO BE USED TO PREVENT UPWARD | | MOVEMENT OF PENDENT SPRINKLERS SUPPORTED WITH STANDARD | | BAND HANGERS. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|