2011-09-22 12:30:44801 SOUTH OLIVE AVENUE - UNITS #806/#807
 PERMIT #11090473
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ELIMINATE ALL SHEET REFERENCES TO NFPA 13R AS THIS
 STANDARD CAN ONLY BE UTILIZED FOR RESIDENTIAL BUILDINGS
 UP TO FOUR STORIES IN HEIGHT. SPRINKLER DESIGN SHALL
 CONFORM TO NFPA 13 WITH THE USE OF RESIDENTIAL
 SPRINKLERS WITHIN DWELLING UNITS.
  
 SPRINKLER PROTECTION IS REQUIRED IN ALL CLOSET SPACES.
 THE EXCEPTION TO NOT LOCATE SPRINKLERS IN SMALL CLOSETS
 24 SQUARE FEET OR SMALLER ONLY PERTAINS TO HOTEL/MOTEL
 OCCUPANCIES.
  
 THE DISTANCE BETWEEN TWO PENDENT SPRINKLERS IN THE
 LIVING/SALON ROOM EXCEEDS 18 FEET.
  
 SPRINKLER COVERAGE APPEARS INADEQUATE BETWEEN THE
 FAMILY KITCHEN AND PANTRY DOOR AREA.
  
 PROVIDE CEILING AND SOFFIT HEIGHTS ON PLANS.
  
 THE HANGER SPACING CHART SHOWS DISTANCES FOR SYSTEM
 PRESSURES LESS THAN 100 PSI. REVISE CHART FOR SYSTEM
 PRESSURE EXCEEDING 100 PSI.
  
 INDICATE THE METHOD TO BE USED TO PREVENT UPWARD
 MOVEMENT OF PENDENT SPRINKLERS SUPPORTED WITH STANDARD
 BAND HANGERS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  