2011-09-20 10:14:532007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED WITHIN 100 FEET OF TYPE C
 TERRAIN THAT EXTENDS MORE THAN 600 FEET WITH A WIDTH
 GREATER THAN 150 FEET. THEREFORE, THE EXPOSURE CATEGORY
 IS C PER FBC R301.2.1.4.3. THE ENGINEERING THAT WAS
 SUBMITTED IS FOR EXPOSURE B. SUBMIT TWO COPIES OF
 ENGINEERING FOR EXPOSURE C.
  