2011-09-15 11:12:311450 CENTREPARK DRIVE - SUITE #250
 PERMIT #11090302
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE. SEVERAL INTERIOR EXIT ACCESS DOORS ARE
 FITTED WITH CARD READERS THAT WOULD PROHIBIT OCCUPANTS
 FREE EGRESS THROUGHOUT THE TENANT SPACE.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 TRAINING ROOM #108 AND CORRIDOR #106 DOORS ARE REQUIRED
 TO SWING IN THE DIRECTION OF EGRESS TRAVEL FOR AN
 OCCUPANT LOAD OF 50 OR GREATER PERSONS PER SECTION
 7.2.1.4.2 OF THE FLORIDA FIRE PREVENTION CODE: NFPA 101
 - LIFE SAFETY CODE.
  
 TRAINING ROOM #108 HAS AN OCCUPANT LOAD EXCEEDING 50
 PERSONS AND THEREFORE WOULD BE CONSIDERED AN ASSEMBLY
 OCCUPANCY. A SECOND EXIT FROM THIS ROOM REQUIRED AS THE
 COMMON PATH OF TRAVEL EXCEEDS 20 FEET.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET E-1: AN ADDITIONAL FIRE ALARM NOTIFICATION
 APPLIANCE IS NEEDED IN CORRIDOR #106 AND OPEN OFFICE
 #116 AS THE EXISTING DEVICE WILL NOT COVER THIS ENTIRE
 SPACE. ALSO, IT WILL BE DIFFICULT TO MEET THE DB
 REQUIREMENT IN TRAINING ROOM #108 WITH A STROBE ONLY
 NOTIFICATION APPLIANCE.
  
 SHEET E-1: NO NOTIFICATION APPLIANCES LOCATED IN OTHER
 COMMON AREAS: COPY #112, MEETING ROOMS #102, #103 AND
 #115.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  