2011-09-16 14:59:15 | BUILDING PLAN REVIEW | | PERMIT: 11090302 | | ADD: 1450 CENTREPARK DR # 250 | | CONT: FISHER CONTRACTING | | TEL: (561)691-4716 | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | * WEST PALM BEACH AMENDMENTS | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | ACTION: DENIED | | SHEET A-2 | | 1) PLEASE SEE TRAINING ROOM # 108 WITH 52 SEATS AND A | | SINGLE EXIT. PLEASE REVIEW 2007/09 FBC-B TABLE 1015.1 | | WHICH REQUIRES 2 EXIT DOORS WITH AN BUSINESS OCCUPANT | | LOAD GREATER THAN 49. | | | | 2) THE TWO DOORS OF TRAINING ROOM # 108 WILL ALSO NEED | | TO SWING IN THE DIRECTION OF TRAVEL PER 2007/09 FBC-B | | SECTION 1008.1.2. | | | | 3) THE EXIT DOOR AT COORIDOR DOOR # 106 WOULD ALSO NEED | | TO SWING INTHE DIRECTION OF TRAVEL. SECTION 1008.1.2. | | | | 4) PLANS INDICATE THE USE OF CARD READERS PLEASE | | PROVIDE COMPLIANCE WITH SECTION 1008.1.8.6. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] |
|