Plan Review Notes
Plan Review Notes For Permit 11090174
Permit Number 11090174
Review Stop E
Sequence Number 1
Notes
Date Text
2011-09-12 11:38:1411090174
 1698 OLD OKEECHOBEE ROAD
 480 VOLT SERVICE
  
 PLEASE ADVISE HOW THIS INSTALLATION WILL COMPLY WITH
 THE FOLLOWING CODE SECTIONS:
  
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE. NEC 230.2
 EACH SERVICE DROP OR LATERAL SHALL SUPPLY ONLY ONE SET
 OF SERVICE ENTRANCE CONDUCTORS. NEC 230.40
 VERIFY THERE ARE NOT MORE THAN SIX SETS OF DISCONNECTS
 PER SERVICE GROUPED IN ANY ONE LOCATION. NEC 210.71
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved