Plan Review Notes For Permit 11090046 |
Permit Number |
11090046 |
|
Review Stop |
ENG |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2012-10-25 14:57:12 | PLEASE INCORPORATE PLANNING'S COMMENTS SO THAT WE MAY | | REVIEW CHANGES. | | | | #1 DRAINAGE: PROVIDE PERVIOUS AND IMPERVIOUS AREA | | CALCULATION FOR SITE. | | | | (STORMWATER RUNOFF FOR DEVELOPMENT WITHIN DEVELOPED | | AREA MUST MEET THE FOLLOWING LEVEL OF SERVICE | | STANDARDS: (A) WATER QUANTITY: POST-DEVELOPMENT RUN-OFF | | SHALL NOT EXCEED PRE-DEVELOPMENT RUNOFF RATES FOR THE | | ENTIRE DEVELOPMENT. (B) WATER QUALITY: THE TREATMENT OF | | POST-DEVELOPMENT RUNOFF FROM THE SITE MUST ENSURE THAT | | RECEIVING WATER QUALITY CRITERIA ESTABLISHED IN CHAPTER | | 17-302, SECTION 17-302.500, F.A.C. ARE MAINTAINED.) | | THE CITY OF WPB REQUIRES THAT APPLICANT ABIDE BY SOUTH | | FLORIDA WATER MANAGEMENT DRAINAGE CRITERIA AS FOLLOWS: | | | | #2 APPLICANTS TREAT FIRST INCH OF RUNOFF WATER OR 2 1/2 | | TIMES THE IMPERVIOUS AREA (EXCLUDING BUILDING AREA), | | WHICHEVER IS GREATER. | | | | (THIS CRITERIA ALSO COMPLIES WITH PERFORMANCE STANDARDS | | ESTABLISHED IN CHAPTER 17-25, F.A.C., WITH TREATMENT OF | | THE FIRST INCH OF RUN-OFF ONSITE TO MEET WATER QUALITY | | STANDARDS REQUIRED BY CH. 17-302, SECTION 17-302.500, | | F.A.C. STORMWATER DISCHARGE FACILITIES MUST BE DESIGNED | | SO AS NOT TO DEGRADE THE RECEIVING WATER BODY BELOW THE | | MINIMUM CONDITIONS NECESSARY TO ASSURE THE SUITABILITY | | OF WATER FOR THE DESIGNATED USE AS ESTABLISHED IN | | CHAPTER 17-302, F.A.C.) | | | | [email protected] | | (561) 494-1085 |
|