2011-09-08 09:14:512007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS
 INCLUDING THE PUMP CURVE FOR THE 2 HP PUMP THAT WILL BE
 INSTALLED.
  
 2) THE PLANS SPECIFY A TDH OF 60 FEET. SUBMIT 2 COPIES
 OF TOTAL DYNAMIC HEAD (TDH) CALCULATIONS FOR THE SYSTEM
 OR DESIGN THE SYSTEM FOR THE MAXIMUM FLOW RATE OF THE
 PUMP.
  