Notes |
Date |
Text |
2011-09-08 09:14:51 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY PLUMBING | | | | 1) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS | | INCLUDING THE PUMP CURVE FOR THE 2 HP PUMP THAT WILL BE | | INSTALLED. | | | | 2) THE PLANS SPECIFY A TDH OF 60 FEET. SUBMIT 2 COPIES | | OF TOTAL DYNAMIC HEAD (TDH) CALCULATIONS FOR THE SYSTEM | | OR DESIGN THE SYSTEM FOR THE MAXIMUM FLOW RATE OF THE | | PUMP. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|