Plan Review Notes For Permit 11080866 |
Permit Number |
11080866 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-09-09 11:39:10 | 4200 NORTH FLAGLER DRIVE | | PERMIT #11080866 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO - SUBMIT REVISED PLANS ADDRESSING | | COMMENTS***** | | | | THE 25 FOOT WIDE ROAD RUNNING NORTH/SOUTH LOCATED | | BETWEEN THE FITNESS BUILDING AND MARINA STORAGE | | BUILDING SHALL BE DESIGNATED AS A FIRE LANE. PROVIDE | | STRIPING AND/OR SIGNAGE INDICATING THIS A FIRE LANE AND | | NO PARKING IS PERMITTED BY ORDER OF THE FIRE MARSHAL. | | | | THE RELOCATION OF THE EXISTING FIRE HYDRANT (EAST OF | | THE CAFETERIA BUILDING) CAUSES THE EXISTING FIRE | | DEPARTMENT CONNECTION FOR THE DOCK (NORTH OF CAFETERIA | | BUILDING) TO BE LOCATED MORE THAN 150 FEET FROM A FIRE | | HYDRANT. | | | | NO OBSTRUCTIONS SHALL BE LOCATED WITHIN 7'-6" OF FIRE | | HYDRANTS. THIS DISTANCE WILL AFFECT TWO PARKING SPACES | | LOCATED ON THE WEST SIDE OF THE CAFETERIA BUILDING. | | | | PROVIDE A FIRE HYDRANT NEAR THE MARINA STORAGE | | BUILDING. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|