2011-08-29 11:56:05 | 222 LAKEVIEW AVENUE - SUITE #810 | | PERMIT #11080760 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | INDICATE IF THIS SPACE IS OBSTRUCTED CONSTRUCTION OR | | UNOBSTRUCTED CONSTRUCTION AND INDICATE THE SPRINKLER | | DISTANCE BELOW THE CEILING DECK. | | | | OCCUPANCY HAZARD NOT INDICATED ON PLANS. IF THIS IS A | | LIGHT HAZARD OCCUPANCY, THE SPRINKLERS SHOULD BE OF THE | | QUICK-RESPONSE TYPE. IF THIS IS AN ORDINARY HAZARD | | OCCUPANCY, SPRINKLER SPACING EXCEEDS 130 SQUARE FEET | | PER SPRINKLER. | | | | INDICATE THE MAXIMUM WORKING PRESSURE FOR THE EIGHTH | | FLOOR. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW |
|