2011-08-29 11:56:05222 LAKEVIEW AVENUE - SUITE #810
 PERMIT #11080760
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE IF THIS SPACE IS OBSTRUCTED CONSTRUCTION OR
 UNOBSTRUCTED CONSTRUCTION AND INDICATE THE SPRINKLER
 DISTANCE BELOW THE CEILING DECK.
  
 OCCUPANCY HAZARD NOT INDICATED ON PLANS. IF THIS IS A
 LIGHT HAZARD OCCUPANCY, THE SPRINKLERS SHOULD BE OF THE
 QUICK-RESPONSE TYPE. IF THIS IS AN ORDINARY HAZARD
 OCCUPANCY, SPRINKLER SPACING EXCEEDS 130 SQUARE FEET
 PER SPRINKLER.
  
 INDICATE THE MAXIMUM WORKING PRESSURE FOR THE EIGHTH
 FLOOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW