2011-08-30 18:11:27 | RESIDENTIAL (R3) ACCORDION SHUTTERS, BUILDING REVIEW |
| CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- CLEARLY IDENTIFY ON ACCORDION SHUTTERS DRAWINGS |
| WHICH SPECIFIC WALL ASSEMBLY (SEE PAGE 9 OF 18) IS |
| GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| OPENING DESIGN PRESSURES, SELECTED ANCHOR TYPE AND |
| SPACING, MAXIMUM SHUTTER SPAN, TYPE OF BLADE |
| LIMITATIONS ETC. SEC 106.1.1 CITY AMENDMENTS TO FBC AND |
| CITY POLICY FOR SHUTTERS INSTALLATION. |
| |
| 2- INSTALLATION SCHEDULE SUBMITTED INDICATES USING ALL |
| POINTS SOLID-SET ANCHORS. TABLES ON SHEET 6 OF 18 AND |
| SHEET 7 OF 18 DON'T ALLOW THE USE OF THIS CONNECTOR ON |
| SOME APPLICATIONS. CLEARLY MARK ON THESE SHEETS WHICH |
| ARE THE APPLICATIONS THAT APPLY USING THE ALL POINTS |
| SOLID-SET ANCHOR TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES, SHUTTERS SPACING AND ANCHOR SPACING. SEC. |
| 106.1.1 CITY AMENDMENTS TO FBC. |
| |
| 3- DESIGN PRESSURES CALCULATIONS DONE BY RAMMS |
| ENGINEERING, INC. NEED TO HAVE ENGINEER'S ORIGINAL SEAL |
| AND SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA |
| STATUTES. |
| |
| 4- FLOOR PLAN SUBMITTED SHOWS 19 OPENINGS, WHILE |
| SHUTTERS INSTALLATION SCHEDULE SHOWS 18 OPENINGS. |
| REVISE/CLARIFY AS REQUIRED. |
| |