2011-08-30 18:11:27RESIDENTIAL (R3) ACCORDION SHUTTERS, BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- CLEARLY IDENTIFY ON ACCORDION SHUTTERS DRAWINGS
 WHICH SPECIFIC WALL ASSEMBLY (SEE PAGE 9 OF 18) IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 OPENING DESIGN PRESSURES, SELECTED ANCHOR TYPE AND
 SPACING, MAXIMUM SHUTTER SPAN, TYPE OF BLADE
 LIMITATIONS ETC. SEC 106.1.1 CITY AMENDMENTS TO FBC AND
 CITY POLICY FOR SHUTTERS INSTALLATION.
  
 2- INSTALLATION SCHEDULE SUBMITTED INDICATES USING ALL
 POINTS SOLID-SET ANCHORS. TABLES ON SHEET 6 OF 18 AND
 SHEET 7 OF 18 DON'T ALLOW THE USE OF THIS CONNECTOR ON
 SOME APPLICATIONS. CLEARLY MARK ON THESE SHEETS WHICH
 ARE THE APPLICATIONS THAT APPLY USING THE ALL POINTS
 SOLID-SET ANCHOR TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES, SHUTTERS SPACING AND ANCHOR SPACING. SEC.
 106.1.1 CITY AMENDMENTS TO FBC.
  
 3- DESIGN PRESSURES CALCULATIONS DONE BY RAMMS
 ENGINEERING, INC. NEED TO HAVE ENGINEER'S ORIGINAL SEAL
 AND SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES.
  
 4- FLOOR PLAN SUBMITTED SHOWS 19 OPENINGS, WHILE
 SHUTTERS INSTALLATION SCHEDULE SHOWS 18 OPENINGS.
 REVISE/CLARIFY AS REQUIRED.
  