2011-08-31 14:54:08 | BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| KITCHENETTE: IF THE KITCHENETTE IS ACTUALLY USED AS A |
| BREAK ROOM THEN COMPLIANCE WITH 2007/ 09 FBC-B 11-4.24 |
| IS REQUIRED. |
| 11-4.24 SINKS. |
| 11-4.24.1 GENERAL. SINKS REQUIRED TO BE ACCESSIBLE BY |
| SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.24. |
| 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE |
| COUNTER OR RIM NO HIGHER THAN 34 INCHES (865 MM) ABOVE |
| THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARANCE. KNEE CLEARANCE THAT IS AT |
| LEAST 27 INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE, |
| AND 19 INCHES (485 MM) DEEP SHALL BE PROVIDED |
| UNDERNEATH SINKS. |
| 11-4.24.4 DEPTH. EACH SINK SHALL BE A MAXIMUM OF 61/2 |
| INCHES (165 MM) DEEP. |
| 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| SINK (SEE FIGURE 32). |
| 11-4.24.6 EXPOSED PIPES AND SURFACES. HOT WATER AND |
| DRAIN PIPES EXPOSED UNDER SINKS SHALL BE INSULATED OR |
| OTHERWISE CONFIGURED SO AS TO PROTECT AGAINST CONTACT. |
| THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER |
| SINKS. |
| 11-4.24.7 FAUCETS. FAUCETS SHALL COMPLY WITH SECTION |
| 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, TOUCH-TYPE, OR |
| ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE |
| DESIGNS. |
| |