Plan Review Notes
Plan Review Notes For Permit 11080715
Permit Number 11080715
Review Stop P
Sequence Number 2
Notes
Date Text
2011-09-30 11:57:252007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE MAXIMUM FLOW RATES FOR THE VARIABLE SPEED PUMPS
 WAS NOT USED IN THE TDH CALCULATIONS AS STATED IN THE
 FIRST REVIEW COMMENT #1.
  
 2) THE MAXIMUM WATER VELOCITY OF 6 FEET PER SECOND IN
 THE 2.5" BRANCH SUCTION PIPING AND THE 8 FEET PER
 SECOND IN THE 2.5" MAIN SUCTION PIPING IS EXCEEDED WHEN
 USING THE MAXIMUM FLOW RATE OF 145 GPM FOR THE VARIABLE
 SPEED PUMPS THAT WERE SPECIFIED. ANSI/APSP-7 SECTION
 4.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]