Plan Review Notes
Plan Review Notes For Permit 11080715
Permit Number 11080715
Review Stop P
Sequence Number 1
Notes
Date Text
2011-09-09 11:55:562007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
 FBC R4101 & ANSI/APSP 7
  
 1) THE PLANS SPECIFY TWO VARIABLE SPEED PUMPS WHICH
 REQUIRE THE MAXIMUM FLOW RATE OF THE PUMP TO BE USED IN
 CALCULATIONS. SEE NOTE NUMBER 1 ON TDH CALCULATION WORK
 SHEET.
  
 2) SPECIFY THE MANUFACTURER, MODEL NUMBER AND HORSE
 POWER OF EACH PUMP. SUBMIT 2 COPIES OF THE
 SPECIFICATIONS FOR EACH OF THE THREE POOL PUMPS
 INCLUDING THE PUMP CURVES.
  
 3) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD (TDH)
 CALCULATIONS FOR EACH OF THE SYSTEMS OR DESIGN THE
 SYSTEMS FOR THE MAXIMUM FLOW RATE OF THE PUMP.
  
 4) SUBMIT A PIPING DIAGRAM THAT SPECIFIES ALL PIPE
 SIZES IN EACH SYSTEM.
  
 5) THE FIRST SHEET OF PLANS SHOWS FIVE SETS OF MAIN
 DRAINS FOR A TOTAL OF 10. THE PIPING DIAGRAM SHOWS FOUR
 SETS OF MAIN DRAINS FOR A TOTAL OF 8. PLEASE CLARIFY.
  
 6) THE VALUE FOR THE SCOPE OF WORK APPEARS TO BE LOW.
 PLEASE SUBMIT A COPY OF THE SIGNED CONTRACT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]