Plan Review Notes For Permit 11080715 |
Permit Number |
11080715 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-09-09 11:55:56 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY PLUMBING | | FBC R4101 & ANSI/APSP 7 | | | | 1) THE PLANS SPECIFY TWO VARIABLE SPEED PUMPS WHICH | | REQUIRE THE MAXIMUM FLOW RATE OF THE PUMP TO BE USED IN | | CALCULATIONS. SEE NOTE NUMBER 1 ON TDH CALCULATION WORK | | SHEET. | | | | 2) SPECIFY THE MANUFACTURER, MODEL NUMBER AND HORSE | | POWER OF EACH PUMP. SUBMIT 2 COPIES OF THE | | SPECIFICATIONS FOR EACH OF THE THREE POOL PUMPS | | INCLUDING THE PUMP CURVES. | | | | 3) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD (TDH) | | CALCULATIONS FOR EACH OF THE SYSTEMS OR DESIGN THE | | SYSTEMS FOR THE MAXIMUM FLOW RATE OF THE PUMP. | | | | 4) SUBMIT A PIPING DIAGRAM THAT SPECIFIES ALL PIPE | | SIZES IN EACH SYSTEM. | | | | 5) THE FIRST SHEET OF PLANS SHOWS FIVE SETS OF MAIN | | DRAINS FOR A TOTAL OF 10. THE PIPING DIAGRAM SHOWS FOUR | | SETS OF MAIN DRAINS FOR A TOTAL OF 8. PLEASE CLARIFY. | | | | 6) THE VALUE FOR THE SCOPE OF WORK APPEARS TO BE LOW. | | PLEASE SUBMIT A COPY OF THE SIGNED CONTRACT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|