2011-08-29 09:41:41 | BUILDING PLAN REVIEW |
| PERMIT: 11080706 |
| ADD: 417 BUNKER RD |
| CONT: WATSON |
| TEL: (561)762-8471 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| 1) NOTE # 7 INDICATES NEW EXTERIOR DOORS, WILL REQUIRE |
| TESTING AND PRESSURES CALCULATED IN ACCORDANCE WITH |
| 1609 , PRODUCT APPROVAL FOR OPENINGS PER : |
| 2007/09 FBC-B 1714.5.4.1ANCHORING REQUIREMENTS |
| 2007/09 FBC-B 1714.5.4.2 MASONRY, CONCRETE OR OTHER |
| STRUCTURAL SUBSTRATE |
| |
| 2) WITH THE REMOVAL OF WINDOWS AND RE-INSTALL OF SAME |
| WINDOWS, IF BUCKS ARE TO BE USED, THE DESIGNER OF |
| RECORD WILL NEED TO PROVIDE THE BUCK ANCHORAGE |
| PER SECTION: |
| 2007/ 09 FBC-B 1714.5.4.1 ANCHORING REQUIREMENTS |
| 2007/ 09 FBC-B 1714.5.4.2 MASONRY, CONCRETE OR OTHER |
| STRUCTURAL SUBSTRATE |
| |