2011-08-30 11:31:19 | REVISION PLUMBING REVIEW. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PLUMBING RISER DIAGRAM SUBMITTED DOESN'T MATCH | | PROPOSED PLUMBING FIXTURES LAYOUT. SEE PROPOSED SECOND | | FLOOR PLAN. REVISE MASTER BATHROOM AND BATHROOM AS | | REQUIRED TO MATCH FLOOR PLAN LAYOUT AND TYPE OF FIXTURE | | SHOWN ON PROPOSED FLOOR PLAN. SEC. 106.1.1 CITY | | AMENDMENTS TO FBC. | | | | 2- PLUMBING RISER DIAGRAM SUBMITTED IS MISSING THE | | LAUNDRY FLOOR DRAIN. SEC. 106.1.1 CITY AMENDMENTS. | | | | 3- SPECIFY ALL PIPE SIZES. SEC. 106.1.1 CITY | | AMENDMENTS. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|