Plan Review Notes
Plan Review Notes For Permit 11080705
Permit Number 11080705
Review Stop P
Sequence Number 1
Notes
Date Text
2011-08-25 17:13:45RESIDENTIAL (R3) REVISION PLUMBING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE COMPLETE PLUMBING RISER DIAGRAM SHOWING THE
 NEW FLOOR DRAIN AND LAUNDRY. ALSO, PROVIDE PLUMBING
 RISER DIAGRAM ADDRESSING PROVISO REQUESTED ON 7/11/11.
 SEE SHEET #4 OF THE ORIGINALLY APPROVED PLANS. NEED TO
 INDICATE CHANGE OF BIDET TO LAVATORY. SEC. 106.3.5.4(9)
 OF CITY AMENDMENTS TO FBC.
 ***NOTE: PLUMBING CONTRACTOR MAY DRAW THE PLUMBING
 RISER DIAGRAM (PROVIDE NAME, SIGNATURE AND LICENSE
 NUMBER).
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712