Notes |
Date |
Text |
2011-10-13 11:58:15 | 1450 CENTREPARK BOULEVARD - SUITE #150 | | PERMIT #11080665 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SHEET A-8: THE COMMON PATH OF TRAVEL FOR SUITE #165 | | STILL EXCEEDS 100 FEET AS THE TWO SUITE ENTRY DOORS ARE | | NOT LOCATED FAR ENOUGH APART TO CONSTITUTE SEPARATE | | EXITS. NO FURNITURE OR EQUIPMENT HAS BEEN SHOWN FOR | | SUITE #165 WHICH MAY ALSO INCREASE THE COMMON PATH OF | | TRAVEL DISTANCE. | | | | SHEET E-2: NO FIRE ALARM NOTIFICATION APPLIANCE | | PROVIDED IN CONFERENCE ROOM #103 OF SUITE #150. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW |
|