2011-10-13 11:58:151450 CENTREPARK BOULEVARD - SUITE #150
 PERMIT #11080665
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-8: THE COMMON PATH OF TRAVEL FOR SUITE #165
 STILL EXCEEDS 100 FEET AS THE TWO SUITE ENTRY DOORS ARE
 NOT LOCATED FAR ENOUGH APART TO CONSTITUTE SEPARATE
 EXITS. NO FURNITURE OR EQUIPMENT HAS BEEN SHOWN FOR
 SUITE #165 WHICH MAY ALSO INCREASE THE COMMON PATH OF
 TRAVEL DISTANCE.
  
 SHEET E-2: NO FIRE ALARM NOTIFICATION APPLIANCE
 PROVIDED IN CONFERENCE ROOM #103 OF SUITE #150.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW