Date |
Text |
2011-08-30 09:49:09 | 1450 CENTREPARK BOULEVARD - SUITE #150 |
| PERMIT #11080665 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| FIRE/SMOKE BARRIER - PROTECT ALL OPENINGS. CHARACTERS |
| SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| STROKE. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| FEET ON CENTER. |
| |
| PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| |
| PROVIDE TACTILE SIGNAGE AT REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| SHEET A-8: THE COMMON PATH OF TRAVEL INDICATED ON THE |
| PLAN EXCEEDS 100 FEET OF LENGTH. |
| |
| SHEET A-8: TRAVEL DISTANCE TO EXTINGUISHERS EXCEED 75 |
| FEET. |
| |
| SHEET E-2: CONFERENCE ROOM #103 AND RECEPTION #101 |
| EQUIPPED WITH CARD READERS PREVENTING OCCUPANTS FREE |
| EGRESS TO A SECONDARY EXIT. |
| |
| SHEET E-2: EXIT ACCESS CORRIDOR IN SUITE #150 EQUIPPED |
| WITH CARD READER ON EGRESS SIDE OF EXTERIOR EXIT DOOR. |
| |
| SHEET E-2: FOUR FIRE ALARM HORN-STROBE DEVICES SHOWN. |
| IT MAY BE DIFFICULT TO MEET THE AUDIBILITY REQUIREMENTS |
| OF NFPA 72 WITH ONLY FOUR AUDIBLE DEVICES. |
| |
| SHEET E-3: NO EXIT SIGNAGE PROVIDED FOR SOUTH OFFICE |
| SPACE IN SUITE #165. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |
| |