2011-08-30 16:12:13 | BUILDING PLAN REVIEW |
| PERMIT: 11080665 |
| ADD: 1450 CENTREPARK BLVD 150 |
| CONT: ANDERSON-MOORE CONSTRUCTION CORP. |
| TEL: (561)662-1819 |
| |
| 2007 FLORIDA BUILDING CODE-BUILDING W/ 2009 FBC |
| SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS CHAPTER 1 |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1450 CENTREPARK #165 11080820- NO FEE PERMIT FOR DEMO |
| OF TENANT SEPERATION WALL AND NEW TENANT SEPERATION |
| WALL, (DRYWALL SCREW INSPECTION) ONLY. |
| COMMENTS FOR BOTH PERMITS 11080665 SUITE # 150 AND |
| 11080820 SUITE # 165 WILL APPEAR UNDER THIS REVIEW. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) THE LIFE SAFETY SHEET A8 INDICATES FOR BOTH SUITES |
| THE COMMON PATH OF TRAVEL IS EXCEEDED. 2007 FBC-B |
| 1014.3 EXCEPTION# 1 DOES ALLOW FOR A 100 FOOT COMMON |
| PATH OF TRAVEL FOR SPRINKLERED BUILDINGS. FOR BOTH |
| SUITES THIS COMMON PATH OF TRAVEL IS EXCEEDED. |
| |
| 2) SHEET A8 THE LIFE SAFETY PLAN INDICATES WITHIN SUITE |
| # 150 SINCE THE COMMON PATH OF TRAVEL IS EXCEEDED, IT |
| WOULD APPEAR THAT A SECOND EXIT DOOR WOULD NEED TO BE |
| INCORPORATED INTO THE PLAN LAYOUT MEETING THE |
| REQUIREMENT OF 1015.2.1 EXCEPTION #3. THE SECONDARY |
| EXIT DOOR CURRENTLY DOE NOT MEET THIS REQUIREMENT. |
| |
| 3) DISCREPANCY IN PLANS PLEASE REVIEW SHEETS A4 VERSES |
| A8 PRINTING ROOM # 116. SHEET A4 INDICATES A DOOR INTO |
| THE EXIT ACCESS CORRIDOR, DOOR # 021 WHICH DOES NOT |
| APPEAR ON SHEET A8. |
| |
| 4) SHEET A8 INDICATES A SEPERATE TENANT SPACE ROOM |
| NUMBER 115 LABELED COURIER, THESE TENANT SEPERATION |
| WALLS ARE NOT INDICATED AS TENANT SEPERATION WALLS. |
| 2007/09 FBC-B 708.1(7). |
| |
| 5) A4 & A8 BOTH INDICATE A NETWORK ROOM # 107, THIS |
| ROOM MAY REQUIRE A 1 HOUR RATING PER NFPA 645.4(5) IF |
| CONSIDERED A IT ROOM? |
| |
| 6) A8 STORAGE ROOM # 117IS OVER 100SQ. FT. AND WILL |
| NEED TO COMPLY WITH 2007/09 FBC-B FOR THE WALL TO BE |
| ABLE TO RESIST THE PASSAGE OF SMOKE SEE TABLE 508.2. |
| WHERE TABLE 508.2 PERMITS AN AUTOMATIC |
| FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE |
| INCIDENTAL USE AREA SHALL BE SEPARATED FROM THE |
| REMAINDER OF THE BUILDING BY CONSTRUCTION CAPABLE OF |
| RESISTING THE PASSAGE OF SMOKE. THE PARTITIONS SHALL |
| EXTEND FROM THE FLOOR TO THE UNDERSIDE OF THE |
| FIRE-RESISTANCE-RATED FLOOR/CEILING ASSEMBLY OR |
| FIRE-RESISTANCE-RATED ROOF/CEILING ASSEMBLY ABOVE OR TO |
| THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, OR SUB |
| DECK ABOVE. DOORS SHALL BE SELF- OR AUTOMATIC CLOSING |
| UPON DETECTION OF SMOKE IN ACCORDANCE WITH SECTION |
| 715.4.7.3. DOORS SHALL NOT HAVE AIR TRANSFER OPENINGS |
| AND SHALL NOT BE UNDERCUT IN EXCESS OF THE CLEARANCE |
| PERMITTED IN ACCORDANCE WITH NFPA 80. |
| |
| 7) 2007/09 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE |
| PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY |
| OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |