Notes
Date Text
2011-08-23 13:37:3811080500
 1320 WILDERNESS DR
 FLORIDA ROOM RENOVATION
  
 PLEASE SUBMIT A PLAN SHOWING THE REQUIRED ELECTRICAL
 OUTLETS FOR THE NEW LIVING AREA.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 ALL NEW GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE
 BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC
 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52
 THE NEW LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR
 LIGHT AND A SWITCHED LIGHT AT OUTSIDE ENTRANCES. AT
 LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED
 OUTSIDE. NEC 210.70
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  