2011-08-23 09:13:18 | 2007 FBC W/2009 REVISIONS |
| |
| 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY |
| IMPACT FEES. |
| |
| 2) THE EXPOSURE CATEGORY SPECIFIED ON SHEET 1 IS |
| INCORRECT. THE STRUCTURE IS LOCATED IN EXPOSURE 'C' PER |
| FBC R301.2.1.4.2. |
| |
| 3) REVISE THE DESIGN WIND PRESSURES FOR THE WINDOWS AND |
| DOORS ON SHEET 1 TO CORRESPOND WITH EXPOSURE 'C'. FBC |
| R301.2.1 |
| |
| 4) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE |
| FLORIDA ROOM AS REQUIRED BY FBCR N1100. THE FORMS ARE |
| REQUIRED TO BE SIGNED BY THE PREPARER AND THE |
| OWNER/AGENT. |
| |
| 5) SPECIFY THE WALL AND CEILING INSULATION FOR THE |
| FLORIDA ROOM ON THE PLANS. |
| |
| 6) PROVIDE DETAILS AND SECTIONS OF THE EXISTING FLORIDA |
| ROOM INCLUDING THE EXISTING FOUNDATION, WALLS, CEILING |
| HEIGHT, ROOF TO WALL CONNECTIONS AND ROOF STRUCTURE ( |
| INCLUDE OVERHANG, ROOF PITCH, ROOF COVERING, ATTIC |
| VENTING, ETC.) FBC R301.1, R401, R601, R801 AND R901 |
| |
| 7) SHOW COMPLIANCE WITH FBC R403.1.4 FOR MINIMUM |
| FOUNDATION DEPTH OF 12" BELOW GRADE. |
| |
| 8) SHOW COMPLIANCE WITH FBC R404.1.6 WHICH REQUIRES THE |
| CONCRETE FOUNDATION TO EXTEND 4" ABOVE GRADE. |
| |
| 9) THE PRODUCT APPROVAL FOR THE PGT FIXED WINDOW |
| (PW-701), NOA NO. 08-1112.10 HAS BEEN SUPERSEDED. THE |
| CURRENT ONE IS NOA NO. 10-0504.05. SUBMIT THE CURRENT |
| NOA THAT HAS BEEN REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD. THE CURRENT NOAS CAN BE FOUND |
| AT THE FOLLOWING WEB SITE : |
| HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP |
| |
| 10) THE INSTALLATION DRAWINGS FOR THE PGT SLIDING GLASS |
| DOOR PRODUCT APPROVAL NOA ARE MISSING HALF OF EACH |
| PAGE. THE COMPLETE DRAWINGS ARE REQUIRED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |