Plan Review Notes
Plan Review Notes For Permit 11080500
Permit Number 11080500
Review Stop B
Sequence Number 1
Notes
Date Text
2011-08-23 09:13:182007 FBC W/2009 REVISIONS
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY
 IMPACT FEES.
  
 2) THE EXPOSURE CATEGORY SPECIFIED ON SHEET 1 IS
 INCORRECT. THE STRUCTURE IS LOCATED IN EXPOSURE 'C' PER
 FBC R301.2.1.4.2.
  
 3) REVISE THE DESIGN WIND PRESSURES FOR THE WINDOWS AND
 DOORS ON SHEET 1 TO CORRESPOND WITH EXPOSURE 'C'. FBC
 R301.2.1
  
 4) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 FLORIDA ROOM AS REQUIRED BY FBCR N1100. THE FORMS ARE
 REQUIRED TO BE SIGNED BY THE PREPARER AND THE
 OWNER/AGENT.
  
 5) SPECIFY THE WALL AND CEILING INSULATION FOR THE
 FLORIDA ROOM ON THE PLANS.
  
 6) PROVIDE DETAILS AND SECTIONS OF THE EXISTING FLORIDA
 ROOM INCLUDING THE EXISTING FOUNDATION, WALLS, CEILING
 HEIGHT, ROOF TO WALL CONNECTIONS AND ROOF STRUCTURE (
 INCLUDE OVERHANG, ROOF PITCH, ROOF COVERING, ATTIC
 VENTING, ETC.) FBC R301.1, R401, R601, R801 AND R901
  
 7) SHOW COMPLIANCE WITH FBC R403.1.4 FOR MINIMUM
 FOUNDATION DEPTH OF 12" BELOW GRADE.
  
 8) SHOW COMPLIANCE WITH FBC R404.1.6 WHICH REQUIRES THE
 CONCRETE FOUNDATION TO EXTEND 4" ABOVE GRADE.
  
 9) THE PRODUCT APPROVAL FOR THE PGT FIXED WINDOW
 (PW-701), NOA NO. 08-1112.10 HAS BEEN SUPERSEDED. THE
 CURRENT ONE IS NOA NO. 10-0504.05. SUBMIT THE CURRENT
 NOA THAT HAS BEEN REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD. THE CURRENT NOAS CAN BE FOUND
 AT THE FOLLOWING WEB SITE :
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
  
 10) THE INSTALLATION DRAWINGS FOR THE PGT SLIDING GLASS
 DOOR PRODUCT APPROVAL NOA ARE MISSING HALF OF EACH
 PAGE. THE COMPLETE DRAWINGS ARE REQUIRED.
  