Plan Review Notes For Permit 11080493 |
Permit Number |
11080493 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-08-19 16:00:23 | BUILDING PROVISO: | | DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL BE BASED | | ON RATIONAL ANALYSIS, USING THE APPLICABLE WIND LOADS | | OF CHAPTER 16 AS SHOWN BELOW: | | 3105.4.2.1 THE WIND DESIGN LOADS FOR ANY FABRIC OR | | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK | | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND | | VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING | | CRITERIA: | | 1. MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90 MPH | | 2. IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN LIFE | | OF 0.77. | | 3. EXPOSURE CATEGORY B FOR OR C AS DEFINED IN CHAPTER | | 16. | | | | |
|